Table 5 - Status Lights

Light Color

On Continuously

Flashing

Red

Restricted (Hard) Lockout

Soft Lockout

Green

Flame Sensed during normal operation
(Could be stray light during standby)

Recycle

Yellow

Control is in Pump Prime mode or
Reset button currently held for 15+ seconds.

N/A

Table 4 - Reset Button Operation

If the burner is in the

below state:

Pushing the reset button will:

Button Click

(press < 1 second)

Button Hold

(press > 1 second)

Button Hold

(press 15+ seconds)

Lockout

Reset from Soft Lockout

Reset from Restricted (Hard)
Lockout

Valve-on Delay, Trial for
Ignition, Ignition Carryover

Go to Pump Prime (see “Priming
the Pump” above)

Disable the Burner:
Any time the burner is running,
press and hold the reset but-
ton to disable the burner. The
burner will remain off as long as
the button is held.

Enables Pump Priming:
After the reset button has been
held for 15 seconds, the button
can then be clicked during the
next ignition sequence to enter
Pump Prime mode.

Run (igniter is shut off)

No action

Motor-Off Delay, Standby

No action

Pump Prime

No action

Exit Pump Prime mode and return to Standby

Reset Button Operation

The table below explains what action the control will take when the reset button is pressed for different lengths of time during the various
burner operating states.

Figure 8. GeniSys Model 7505 Control

Section: Burner Control

Display Module:
Permanent device for programming
and diagnostics

Alarm Module:
For adding isolated low voltage alarm
contacts to the base control. See Alarm
Module Instructions for specifi cations.

Contractor’s Tool:
Hand-held device for
programming and diagnostics

Cad Cell
Connections

Wiring
Connections

Communication Port 2

Reset Button with Red Light

Communication Port 1

Thermostat Terminals

Green Light

Yellow Light