Note: in Massachusetts, the following must be done:

 Tempered potable water must meet temperatures in 248 CMR.
 All water piping must be insulated in accordance with 780 CMR (Massachusetts energy code).
 50 feet maximum distance from water heater to space heating load (developed length).
 Piping loop between water heater and heating load must be in compliance with 248 CMR.
 All circulators must use an electronically controlled timer that activates every 6 hours for 60 seconds.


Figure 7.

Recommended Piping for Combination Water and Space Heating Applications.