SECTION 7.

Maintenance

7.1 System Maintenance

1. Lubricate the system water-circulating pump, if

required, per the instructions on the pump.

2. If a strainer is employed in a pressure reducing

valve or the piping, clean it every six months.

3. Inspect the venting system for obstruction or

leakage at least once a year. Periodically clean

the screens in the vent terminal and combustion

air terminal (when used).

4. Keep the appliance area clear and free from

combustible materials, gasoline, and other

flammable vapors and liquids.

5. If the appliance is not going to be used for

extended periods in locations where freezing

normally occurs, it should be isolated from the

system and completely drained of all water. All

systems connected to it should also be drained or

protected from freezing.

6. Low water cutoffs, if installed, should be

checked every 6 months. Float type low water

cutoff should be flushed periodically.

7. Inspect flue passages, and clean with brushes/

vacuums, if necessary. Sooting in flue passages

indicates improper combustion. Determine the

cause and correct.

8. Inspect the vent system and air intake system,

and if the vent system is Category III, ensure

that all joints are sealed properly. If joints need

to be resealed, follow venting manufacturer's

instructions to clean and reseal vent system.

7.2 Appliance Maintenance and

Component Description

Only genuine Bradford White replacement parts should

be used.

Caution

Label all wires prior to disconnection when

servicing controls. Wiring errors can cause

improper and dangerous operation. Verify proper

operation after servicing.

Attention

Lors d’entretien ou de réparation des commandes,

étiquetez tous les câbles avant de les

déconnecter. Des erreurs de câblage peuvent

provoquer des fonctionnements incorrects et

dangereux. Après toute intervention d’entretien

ou de réparation, vérifier que l’appareil fonctionne

correctement.

The gas and electric controls on the appliance

are engineered for long life and dependable operation,

but the safety of the equipment depends on their

proper functioning. It is strongly recommended that

a qualified service technician inspect the basic items

listed below every year.

a. Ignition control

b. Ignitor

c. Water temperature control

d. Automatic gas valve

e. Pressure switches and tubing

f.

Blower

6.7 Shutting Down the Brute Deluxe

1. Switch off the main electrical disconnect switch.

2. Close all manual gas valves.

3. If freezing is anticipated, drain the Brute Deluxe

and be sure to also protect building piping from

freezing.

This step to be performed by a qualified

service person.

6.8 To Restart the Brute Deluxe

If drained, follow

Section 6.1

in this manual for

proper filling and purging.

1. Switch off the main electrical disconnect switch.

2. Close all manual gas valves.

3. WAIT FIVE (5) MINUTES.

4. Set the aquastat or thermostat to its lowest

setting.

5. Open all manual gas valves.

6. Reset all safety switches (pressure switch, manual

reset high limit, etc.).

7. Set the temperature controller to the desired

temperature setting and switch on electrical

power.

8. Burner will go through a pre-purge period and

ignitor warm-up period, followed by ignition.