beautypg.com

Bradford White BMT2V0400 User Manual

Page 28

background image

B

radford

W

hite

C

orp.

Page 28

differential/2.

2. Target Max - The boiler target maximum is

the point at which the stages will start to turn off to

maintain a maximum water temperature. The Boiler

Maximum water temperature is set by setting dip

switch #4: Boiler Maximum 210°F (Off) / 190°F (On).

To ensure that the water temperature is less than

the Boiler Maximum water temperature the target is

decreased to allow the stages to cycle off by the Boiler

Maximum water temperature, Boiler Maximum target

is set to Boiler Maximum - differential/2.

Auto Differential The control automatically

adjusts differential to prevent short cycling and

maximize the lifetime of components.

WWSD Operation Warm Weather Shutdown -

WWSD feature is selected via dip switch #3, WWSD

Inactive (Off) / Active 70°F (On). WWSD point is

fixed at 70 deg F. Control exits WWSD when the

outdoor temp falls to 65 F. When there is a call for

HEAT and the control is in WWSD the HEAT call will

be ignored. When there is a call for DHW and the

control is in WWSD the DHW call will be satisfied.

WWSD LED turns on when control detects WWSD.

Summary of Input Sensors:

1. Outdoor sensor - monitors the outside air

temperature for outdoor reset mode

2. Boiler outlet sensor -monitors the water

temperature of the boiler outlet supply

3. System Supply sensor - monitors the water

temperature of the system supply

The boiler outlet sensor is required at all times.

If the boiler outlet sensor has any fault then the control

will flash an error and turns all stages off. The system

supply sensor is optional and utilizes

primary / secondary piping. If the system supply

sensor has a fault then the control flashes an error

message and operates using the boiler outlet sensor

(system supply = boiler outlet).

6.3 External Boiler Operations

Use the field interlock ( T-T terminals ) that are

inside control box.

6.4 Sequence of Operation

If a field-supplied pump is properly wired to the

unit, or if the unit is pump-mounted, the pump will be

energized.

Once the water flow switch makes, if all of the

safety interlocks are closed, the ignition module will

energize the blower(s) for a 15-second pre-purge,

followed by a 40-second period to allow the ignitor to

heat.

The ignition control energizes the blower. The

blower pressurizes the air box (which supplies air to

the burners) and closes the normally-open contact

on the airflow pressure switch. The blocked vent

pressure switch senses the pressure in the exhaust

plenum. This switch opens if the pressure is excessive

(as an indicator of a blocked vent). When these two

pressure switches are closed, voltage is sent to the

PSW terminal on the ignition control, which allows the

ignition module to proceed with the ignition sequence.

If the airflow proving circuit is not proven,

ignition module will lock out.

Section 6.5

describes

the result of air flow faults in more detail.

When the ignition control gets the signal at the

PSW terminal, it will energize its MV terminal, which

sends power to the stage one (or on/off) main valve.

After a 7-second trial for ignition, the ignitor

switches to flame sense mode. If a flame is not

detected, the gas valve will close and the ignition

module will attempt ignition again (up to two more

times, for a total of three attempts.) If all three

attempts fail, the ignition control will lock out.

If flame is sensed, the burner will continue to

fire as long as there is a call for heat, and none of the

safety circuit is interrupted.

If there is a call for stage 2 on a 2-stage unit, that

valve will be energized.

If there is a loss of flame signal during a

successful firing sequence, the ignition control will

remove power from the gas valves, and then attempt

to light up to two more times. If successful, the Brute

Deluxe will fire normally. If unsuccessful, the ignition

control will lock out.

When the call for heat is satisfied, the gas

valve(s) closes, and the blower starts a 45 second

post-purge, and the pump starts the post-purge (where

applicable).

6.5 Ignition Control Reaction to Air Flow /

Blocked Vent Pressure Switch

Air flow and blocked vent status are continuously

monitored by the Brute Deluxe ignition control, at the

control’s PSW terminal.

At the start of an ignition sequence, if the ignition

control sees power at PSW for 30 seconds, but the

combustion blower has not yet been energized by the

control (F1 and F2), the ignition control will remain

in this fault mode, with the blower off. If the power to

PSW is removed while there is still a call for heat, the

ignition sequence will start again, but the main valves

will not be energized until PSW sees power during the

ignition sequence.

If the PSW signal is lost while the Brute Deluxe

is firing, the control will immediately de-energize the

gas valve terminal (MV). The blower will remain on

for the post-purge period (45 seconds), and the control

will continue to monitor the PSW input. If the signal

is detected during the post-purge period, a normal trial

for ignition will begin, starting with the 15-second

pre-purge. If the signal is not detected during the post-

purge, the control will lockout with the blower off.

This manual is related to the following products: