SERVICE PROCEDURE V

Gas Control

Testing, Disassembly & Replacement

TEMPERATURE SENSOR TESTING

Temperature Sensor Testing

Following “Gas Control

Disassembly/Reassembly”

instructions, disassemble Gas

Control to access temperature

sensor.

N

Y

Using a multi-meter set to the ohms setting, insert one meter probe (see caution)
into center wire position of thermal well connector, insert the second probe (see
caution) into either of the outside wire positions (see photo on left).

Alternate the probe on the outside position to the opposite outside wire position
(see photo on right).

Replace temperature

sensor

With the temperature sensor still

in the back plate, use a multi-

meter set to the Ohms setting,

determine the resistance of

temperature sensor

(see caution and photos above)

Replace Gas Control

Once the temperature sensor resistance values are known, the

water temperature must also be known to determine if the

resistance values are correct. See next page to obtain water

temperature.

Are temperature sensor resistance values correct?

CAUTION

DO NOT use standard multimeter probes for this test.
Doing so will damage connector. Use special pin type
electronic probes or small diameter wire pins inserted
into connector.

If Control has gone into lockout due to excessive tank

temperature (four flash, three second pause) reset

control by rotating gas control knob to “OFF” position

and wait a minimum of (5) minutes. Then follow lighting

instructions and return gas control knob to desired

setpoint.

Observe Green LED indicator.

Does error code 4 (four flash, three

second pause) continue?

Resume normal operation.