ELECTRICAL AND LOW VOLTAGE BOXES
In order to make all faceplates flush with the ELiTE CFS fabric surface, there must be a solid base for them to rest on, over
the stretched fabric. In most cases, the tallest edge of all junction boxes must be 1” to 1¹⁄₈” above the drywall surface. This should
be done as part of the standard room preparation for ELiTE CFS installation. Shown here are some examples of how junction
boxes and faceplates are handled for an ELiTE CFS installation.
1
"
drywall
Low Voltage or 110V
Extra deep box mounted to
extend 1" beyond wall
surface. Retainer used to
secure fabric, and provide
solid mounting of faceplate
1
"
drywall
Low Voltage or 110V
Extra deep box with shims
installed by Auralex.
Fabric is simply cut
around electrical device.
Shim holds fabric flush.
shim
1
"
drywall
Low Voltage Only
In some cases, low
voltage boxes may be
left flush with wall, and
plate attached with extra
long screws.
shim
Side view of trim detail for
intersection of vertical wall and
45° angle ceiling.
NOTE: shim is not installed
directly into the intersection of
the surfaces. This type of detail
should be coordinated carefully
with Auralex.
1
"
drywall
110V Box With Extender
Standard box, with
extender. Auralex
installs shims.
shim
electrical box
1
"
box
extender