Deg F or Deg C
Setting 1
Press the “Down” arrow to change temperature
from Deg F to Deg C.
Press the “Up” arrow to change temperature
from Deg C to Deg F.
Low temperature
alarm set point
Setting 2
Press “Mode” button to advance to Setting 2.
Press the “Up” or “Down” arrow buttons to
adjust to the desired set point. Factory default
is 50 Deg. F.
Setting 3
Press “Mode” button to advance to Setting 3.
Press the “Up” or “Down” arrow buttons to
adjust to the desired set point. Factory default
is 65 Deg F.
Low humidity
alarm set point
Setting 4
Press “Mode” button to advance to Setting 4.
Press the “Up” or “Down” arrow buttons to
adjust to the desired set point. Factory default
is 5%.
High humidity
alarm set point
Setting 5
Press “Mode” button to advance to Setting 5.
Press the “Up” or “Down” arrow buttons to
adjust to the desired set point. Factory default
is 95%.
Add or remove
humidifier
Setting 6
Press “Mode” button to advance to Setting 6.
Press the “Up” or “Down” arrow buttons to
adjust to the desired set point. Factory default
is zero (0).
Zero (0) = No humidifier
Two (2) = Stand-alone remote mounted
humidifier
Fan AUTO or ON
Setting 7
Press “Mode” button to advance to Setting 7.
Press the “Up” or “Down” arrow buttons to
adjust number to the desired set point. Factory
default is zero (0).
Zero (0) = Auto – fan only turns on when
there is a call for cooling or heating
One (1) = Fan On – fan remains on
continuously