High pressure switch has shut the unit down, Instructions to reset high pressure switch – Vintage Cellars Wine Guardian Water-Cooled Cooling System User Manual
Page 51

48
High Pressure Switch has Shut the Unit Down
Every Wine Guardian unit has a manual reset high pressure switch in the refrigeration system. This
switch shuts the compressor and condenser down if the head pressure in the system is too high. It is
intended to protect the compressor. Restricted airflow through the condenser is the most common reason
for the pressure to become too high. This can be caused by dust covering the filter or an obstruction
blocking the airflow in the duct or grille.
Possible Cause
Solution
Head Pressure in unit is too high because
Remove the obstruction in the duct or grille or
an obstruction is restricting air flow through
clean the filter. Then restart the unit after
resetting the using the high pressure switch.
Instructions to Reset High Pressure Switch
√ Remove the access panel, grille or duct collar at the condenser opening labeled “High
Press. Manual Reset Switch -----> Remove panel or grille to access”
√ Locate the high pressure switch near the compressor (a cylindrical device piped into
the refrigeration system with two wires and a red button on the top).
√ Push in the button until it locks into position.
√ Push the rocker switch to restart the unit.