beautypg.com

Installing the condensing unit – Vintage Cellars Platinum Split Tech Manual User Manual

Page 33

background image

www.whisperkool.com | Page 31

Evacuation

Connect evacuation type four valve gauge manifold to high and low pressure service valve ports on the condensing

unit with the valve stems mid seated as when leak testing. Install service caps on valves and tighten them. Energize

the liquid line solenoid valve (make sure there is fresh oil in the vacuum pump). Connect a micron gauge directly to

the pump, blank off and start the pump to verify that it is capable of 200 micron vacuum and the gauge is capable of

reading that vacuum. Connect the micron gauge to the access valve installed in the suction line at the Evaporator Unit

(Fan Coil Unit). Remove the Schrader valve depressors from the gauge hoses to reduce restriction and connect gauges

to the suction and liquid line service valve service ports on the condensing unit. Connect the pump to the 3/8” hose

on the manifold set, start the pump and run until the micron gauge reads 200 microns.

When a 200 micron level evacuation is achieved, break the vacuum with R-134a and add enough refrigerant to

pressurize the system with a few psi of positive pressure.

Charging

Remove the vacuum pump and the micron gauge. Install a spare low pressure gauge to the access valve at the

Evaporator Unit (Fan Coil Unit). With the power off to the condensing unit, place the cylinder of R134a on a digital

scale. Admit liquid refrigerant to the system through the high pressure side,

(Liquid line service valve) until the refrigerant stops flowing or until about three pounds have been added. Shut off

refrigerant flow to system.

Verify that the set point on the controller is low enough to allow the system to run continuously for 30 minutes or

more. Turn on power to the condensing unit and the compressor should start if suction pressure is above 6 psi. If the

system pumps down and the compressor shuts off, set the 5 minute time delay relay time to the lowest setting to

avoid having to wait. Add refrigerant as a vapor through the low pressure side of the system (suction service valve

port).

Observe the sight glass when the compressor starts. If bubbles are present, slowly add more refrigerant in vapor form

to the low side. The suction pressure and head pressure should increase as the sight glass clears. Check the superheat

during the charging process. If the superheat drops to 4 or 5 degrees Fahrenheit and sight glass still has bubbles, let

the unit run until the wine cellar temperature drops and approaches 55 degrees Fahrenheit. Observe the sight glass,

if bubbles are present add additional refrigerant in small increments. Let the system stabilize for about 5 minutes

and check the sight glass for bubbles before adding additional refrigerant. Once the sight glass is clear, check the

superheat at the outlet of the Evaporator Unit (Fan Coil Unit) (evaporator superheat should be between 8-12 degrees

Fahrenheit). If superheat is not between 8 and 12 degrees make an adjustment to the expansion valve. Depending

temperature, the “high side” should be approximately 175lbs, and the “low side” should be 28lbs or more to keep the

Evaporator Unit (Fan Coil Unit) from icing.

INSTALLING THE CONDENSING UNIT