beautypg.com

Preparing the condensing unit (continued) – Vintage Cellars Platinum Split Tech Manual User Manual

Page 30

background image

Page 28 | 1-800-343-9463

PS

033114

PREPARING THE CONDENSING UNIT (continued)

It is required to size the suction line tubing according to this chart.

Installing the Condensing Unit

The condensing unit can be installed inside a well ventilated area of the home, but it is typically installed outside.

Exterior applications will require the use of a protective housing, and the amount of sun exposure should be

considered when selecting the placement of the condensing unit .The condensing unit requires a dedicated 20 amp

circuit, non-GFI. Make sure there is a minimum three-foot horizontal clearance in front and rear of the unit. The unit

may either be hard wired or plug-in depending on local electrical codes.

Set the condensing unit level and with proper clearances in accordance with the instructions, name plate power

supplied, proper electric disconnect and fuse protection connected but not turned on and ready for piping

connections.

Inside Condensing Unit Installations: Inside installations require special consideration, as there must be

adequate ventilation to remove the heat created during normal operations. An exhaust port with fan may

need to be installed to ensure that heat is effectively removed from the utility room. A return grille or provision

for 500 - 600 cfm of cool air to enter the room to replace the exhausted air will accomplish this. Unobstructed

airflow to and from the unit is a critical factor in the unit’s overall performance. Make sure there is a minimum

three-foot horizontal clearance in front and rear of the condensing unit and at least one foot on each side. This

will assure that the unit can move the air around the room in an efficient manner.

Outdoor Condensing Unit Installations. You must utilize the exterior condensing unit housing for outdoor

installations. Place the condensing unit on a solid foundation in a location with adequate ventilation. There

should be three feet of clearance in the front and rear of the unit and one foot on each side. The unit should

be elevated 18 inches in order to avoid any possible flooding or damage by animals, and should be clear of

leaves, dirt, and other debris.

Head Pressure Control, Fan Cycling Switch:

These switches are used to cycle the condenser fan at low ambient temperature conditions. If your unit is equipped

with a Low Ambient Control, set the switch to 170 psig for cut-in and 70 psig for the differential. Further adjustment

may be needed. Verify the settings via refrigeration gauge and perform the final adjustments to the readings on the

gauge manifold set. If your condensing unit is not equipped with an adjustible Low Ambient Control, it features a pre-

set Fan Cycling Switch. These controls serve the same purpose, but have different names.

Refrigeration Lines

A 1/4 inch O/D copper “liquid line” is required

The refrigerant drier and the sight glass shall be installed (in that order) in the direction of the refrigerant flow in the

liquid line between the condensing unit and Evaporator Unit (Fan Coil Unit). Enclose the suction line in a cellular

insulation ½” wall thickness Armaflex (brand name) or equal to reduce heat transfer.

Model

Line Set Length

<25ft

26-50ft

50-100ft

Vertical Rice

<3ft 3-10ft >10ft

<3ft 3-10ft >10ft

<3ft 3-10ft >10ft

Platinum Split 4000

Horizontal Tubing

1/2”

5/8”

Vertical Rise

3/8”

5/8”

5/8”

1/2”

Platinum Split 8000

Horizontal Tubing

1/2”

5/8”

Vertical Rise

1/2”