SIZING A COMMON VENT MANIFOLD SERVING MULTIPLE DRYERS

The most important step towards assuring that individual dryers vented into a common manifold exhaust smoothly is to size the
manifold large enough to reduce the affects that velocity in the manifold has on the junctions of the dryer vent connections.

Exhaust moving too quickly in a common vent manifold can amplify the exhaust at vent connectors by aspirating across the con-
nector opening and creating an amplified siphon affect. With a properly sized common vent manifold, velocities are maintained
below the point where they have a significant affect on the exhaust of the individual dryer connections.

It is important to note that these sizing recommendations are for the common vent manifold only and that typically the smaller mini-
mum vent diameter listed in the RT-Series Fan selection table may be used for the remainder of the horizontal vent and chimney.
The larger diameter vent manifold should extend at least 2 diameters beyond the last dryer connection point.

1. When in doubt, get help from Tjernlund Tech Service at 800-255-4208, push 0 and ask for technical assistance or email

[email protected] with details of the job.

2. When possible use 45o Manifold Tee connections to the common vent manifold in the direction of the RT-Series Fan instead of

90o Tee connections. This will reduce the aspiration effect.

3. If possible, locate larger exhaust volume vent connections closer to the RT-Series Fan. This reduces the affect of their exhaust

on smaller volume connections.

4. The size of the common vent manifold should be at least 90% of the total area of all individual vent connections. See example

below.

Example: A vent layout is required for a
job that consists of 3 dryers with 6” diameter outlets.

Add these areas together:

3 x 0.1964 = 0.5892

Total Area = 0.5892 Square Feet x 0.90 (90%) = 0.530. In looking at the table above, this area is greater than an 8" diameter pipe
but smaller than a 10" diameter pipe. 10" diameter vent is the minimum size the common vent manifold diameter should be. It is
perfectly acceptable to be larger than this area if desired. It is also acceptable to have this area be reduced as the vent system
works backward towards the appliance furthest from the RT-Series Fan. In this example, the common vent manifold should extend
at least 20" past the connection point of the dryer farthest from the RT-Series Fan.

COP2 INSTALLATION

The COP2 is intended for indoor installation only. Do not mount the COP2 on a heat source or in an environment that exceeds

104oF (40oC). Examples of improper mounting surfaces include vent pipe, top of heater casing or any place where radiant or
convective heat would cause the junction box temperature to exceed temperature limits.

Using the key hole slots on the back of the COP2 junction box as a template, mark (4) holes on the mounting surface, drill 1/4”
pilot holes for wall anchors if necessary, and secure junction box using provided screws.

PRESSURE SENSING TUBE INSTAL-

LATION

Breech Size Diameter Area (Square Feet)

3”

0.0491

4”

0.0873

5”

0.1364

6”

0.1964

8”

0.3491

10”

0.5454

12”

0.7854

14”

1.0690

16”

1.3960

18”

1.7670

20”

2.1820

D

2D

MINIMUM

2D

MINIMUM

COMMON VENT MANIFOLD

MAINTAIN THE DRYER

OUTLET DIAMETER UNTIL

THE COMMON MANIFOLD

FIGURE 8054009 4/14/11

DRYER FURTHEST

FROM THE INDUCER

SENSING TUBING

TO XCOP1

DRYER FURTHEST

FROM ROOFTOP FAN