beautypg.com

Smart Power Systems HR-30 (3-Phase) User Manual

Page 50

background image

Smart Power

®

Systems

A. C. MODULAR GENERATOR SYSTEM

Page 49 of 52


2.

2. Adjust pump compensator:

a. Reference Figure 30.

b. Loosen the flow control pressure jam nut.

c. While monitoring the generator’s output voltage, slowly rotate the flow control

set screw with a 4mm hex wrench. Adjust the flow control until the generator’s
output frequency is 63 Hz.


d. While keeping the setscrew from rotating, with the hex wrench, re-tighten the

jam nut.

Pump assembly

Figure 30