Page 36 of 52

g. If the hydraulic fluid appears dirty or black in the reservoir sight gage, replace

the fluid and filter immediately. Also, if the hydraulic fluid sustains a temperature
over 175° F, replace the fluid immediately. Oxidation can occur naturally over
time and can be accelerated with over temperature operation, affecting
generator output. Always change the filter when the hydraulic fluid is changed.


WARNING:


When adding or replacing hydraulic fluid, always use clean, new Dexron III fluid.

Do not power wash the generator. Doing so will void the system’s warranty.

Do not allow liquid to enter the generator.

If the outside of the generator requires cleaning, wipe surface with a damp cloth.

Clean the Command and Control Center using soap and water with a soft cloth only.
Improper cleaning, handling and use that may scratch, gouge, chip, fade or
otherwise damage the metallic coating and display surfaces are not covered under
the device warranty.


2.

Replace the oil filter after every 250 hours of operation, or every three (3) years
(whichever comes first). Use Dexron III fluid and one of the following filters:

Hydac 0085 MA010 P


Lubricate the oil filter gasket with Dexron III before installation to permit
proper sealing of the filter.


WARNING:


Do not by-pass the filter or alter filtration plumbing in any way. Doing so will void
the system’s warranty.


3.

The system controller automatically records the time from the previous filter change.
The hours since the previous filter change can be accessed using the Command &
Control Center by pressing the Mode switch until the following screen appears
(reference Figure 25):