2.

Adjust pump compensator:

a. Loosen and remove flow control cap. Reference Figure 30.

b. Loosen the flow control pressure jam nut.

c. While monitoring the generator’s output voltage, slowly rotate the flow control

set screw with a 3mm hex wrench. Adjust the flow control until the generator’s
output frequency is 64 Hz.


d. While keeping the setscrew from rotating, with the hex wrench, re-tighten the

jam nut.


e. Replace and tighten the flow control cap.


Pump assembly