A. C. MODULAR GENERATOR SYSTEM
Page 40 of 53
Diagnostic Faults:
The following is a list of the diagnostic faults, with a brief explanation of each.
String Class
Meaning
Alarm
The control valve feedback is invalid, indicating the system is not
under control. Voltage and/or Frequency may be out of
specifications.
Override Overcurrent condition. The line in which the overcurrent
condition exists is indicated by the location of the “
” string: If in
the “Amps Line 1” field, the overcurrent is in line 1; If in the
“Amps Line 2” field, the overcurrent is in line 2.
Alarm
Current sensor fault on line 1. The indicated current may be
incorrect.
Alarm
Current sensor fault on line 2. The indicated current may be
incorrect.
Override
Voltage Sensor Fault. The indicated voltage may be incorrect.
Alarm
Oil temperature is getting too high (>175° F). Measured
Temperature in the “Hours” field
Override
Oil Temperature is too high (>180° F). Measured Temperature
in the “Hours” field.
Override
Oil level in reservoir is low. Add oil to clear the error.
Shutdown Oil Temperature dangerous (>220° F). Measured Temperature
in the “Hours” field.
Alarm
Indicator Light Ground Fault. The indicator light may not
function properly.
Alarm
Temperature Sensor Fault. The indicated oil temperature may
be incorrect.
Alarm
Buzzer Ground Fault. The audible alert buzzer may not function
properly.
Alarm
Display Ground Fault. The Command & Control Center may not
operate properly.
Alarm
Low Side Fan Short. The Fan may not operate properly
Service
Warning /
Override
Service Warning: Change the Oil Filter
Override There is an electrical load imbalance of more than 20% of the
systems’ rating between Line 1 and Line 2
Table 2