Install the connecting pipe, The procedure of connecting pipes 7.1, Caution – Pridiom Cassettes PCM183HX Installation Manual User Manual
Page 16

15
installation manual
Foundation could be on flat and is recommended be 100-300mm
higher than ground level.
Install a drainage around foundation for smooth drain
When installing the outdoor unit fix the unit by anchor bolts of
M10.
When installing the unit on a roof or a veranda,drain water
sometimes turns to ice on a cold morning. Therefore, avoid
draining in an area that people often use because it is slippery.
1
2
3
4
1
The Procedure of Connecting Pipes
7.1
All field piping must be provided by a licensed
refrigeration technician and must comply with the
relevant local and national codes.
Prevent let air, dust, or other impurities enter the pipe
system during installation.
Insulation pipe shall be used to the gas piping and the
liquid piping. Otherwise, the condensate may happen
CAUTION
7. INSTALL THE CONNECTING PIPE
Check whether the height drop between the indoor unit and
outdoor unit, the length of refrigerant pipe, and the number of
the bends meet the following requirements:
(The number of the bends less than 15.)
unit: m
Concrete Foundation
1. Suspend the unit as the drawing indicates.
2. Ensure that ceiling can resist the Outdoor unit weight indicated
in specification label plate.
Suspended unit
No
Description
1 Outdoor Unit
2
Vibration-proof rubber
3 Anchor Bolt M10
4 Drainage (Wide 100×Depth 150)
5 Drainage
6 Mortar Hole (Φ100×Depth 150)
Sling Bolt
Suspension Bracket
Table 6-4
Table 6-5
mm
MODEL
Unit
B
C
1120
720
1328
740
1338
820
18~24
30~36
48
Fig.6-16
Fig.6-17
≥100
0 0
1
0 0
3
Table 7-1
R410A
Drill a hole in the wall (suitable just for the size of the wall
conduit), then set on the fittings such as the wall conduit and
its cover.
Model
12K
18K-24K
30K-42K
12K
18K-24K
30K-60K
48K-60K
12K
18K-24K
30K
48K-60K
36K
50Hz T1 condition/R22
Split type heat pump
50Hz Vertical discharge heat pump
/60Hz T1 condition/R22 Split type
heat pump and Vertical discharge
heat pump
The type of models
R410A inverter Split type heat pump
and Centrifugal fan outdoor unit
50
50
30
15
50
30
15
30
30
25
10
25
R410A Split type heat pump
and and Centrifugal fan outdoor
unit
50Hz/60Hz T3 condition
(outdoor unit down)
50Hz/60Hz T3 condition
(outdoor unit up)
the unit with quick joint
12K
48K-60K
18K-30K
36K
18K-24K
42K-60K
30K
36K
18K-24K
12K-18K
48K-60K
42K
30K
36K
50
25
15
30
50
30
25
30
25
50
30
30
50
15
35
5
5
25
20
30
25
15
8
20
25
15
10
20
20
25
12
5
15
25
10
8
20
10
8
20
refrigerant pipe
The length of
height drop
The max