VEZ-4x Series, 2-Way/3-Way, NPT Zone Control Valves (1/2 to 1")

2

Installation Guide

G

G0

(Red Wire)

(Black Wire)

24 VAC

Neutral

L

N

(Black Wire)

(White Wire)

120 VAC

Neutral

(Green Wire)

GND

24 VAC Fail-Safe (Spring Return)

Actuator “M” MEP-3503 (NO or Fail AB-A)

Actuator “N” MEP-3501 (NC or Fail AB-B)

120 VAC Fail-Safe (Spring Return)

Actuator “P” MEP-3504 (NO or Fail AB-A)

Actuator “Q” MEP-3502 (NC or Fail AB-B)

From Class 2

Transformer

Wiring

+

Y

G0

G

24

VAC

Class 2

Transformer for

24 VAC Power

Proportional (Fail-In-Place)

Actuator “A” MEP-3516 (NO or 0 VDC = AB-A)

Actuator “B” MEP-3511 (NC or 0 VDC = AB-B)

24

VAC

Y2

Y1

G

Neutral

Tri-State (Fail-In-Place)

Actuator “F” MEP-3510

0–10 VDC

Class 2

Transformer for

24 VAC Power

Neutral

Terminal

Plug

Terminal

Plug

Terminal

Plug

Block

Cover

See the appropriate diagram.
NOTE: All wiring must conform to NEC and local

codes and regulations.

NOTE: For 120 VAC spring return actuators, the

wiring connection requires a junction box

and flex conduit.

NOTE: For 24 VAC actuators, use Class 2

transformers. For 24 VAC spring return

actuators, connections to the wire leads

can be made inside the housing (remove

the two screws and pull the housing off to

access the interior).

CAUTION

For proportional actuators, wire connection
on G is 24 VAC HOT, not ground! G0 and G
must be properly wired for correct function
and full life of the actuator.

Two-Position Spring Return