1. Clean the lines upstream from the valve. Remove

any debris (welding slag, pipe scale, or other

contaminants) larger than 1/16 inch (1.6 mm).

NOTE: If the system experiences large amounts

of debris, steps should be taken to keep

the system clean, such as 20 mesh strainer

installed upstream of the valve.

2. Align the valve assembly according to the system

flow requirements. VEF-56 three-way valves can

be used in either mixing or diverting applications

(see the VEF-56 3-Way Details section).

NOTE: No flange gaskets are needed because of the

design of the seat face.

3. The valve may be mounted on either vertical or

horizontal pipe lines. On horizontal lines, mount

the valve so the actuator is positioned upright and

over the valve. (Leave sufficient room on all sides

to service the actuator and valve.)

CAUTION

To prevent condensation from dripping onto the
actuator housing on horizontal lines, mount the
valve with the actuator in the upright position or, at
most, at a 90° angle. See the Mounting (2-Way and
3-Way) illustration below.

4. Bolt the valve to the pipes.
5. Eliminate air from the system to keep the valves

full of fluid during operation.

2-Way and 3-Way Rubber-Lined Butterfly Valves

VEF-53/56 Series

2-Way Action:

CCW to Close

Up

(for horizontal

lines) or up

to 90° angle

3-Way Action:
With Actuator Full
CCW, Master
Valve is Closed
and Slave Valve
is Open

VEF-56

Arrangement

Master

Valve

(Actuator)

Slave

Valve

Common

Port

1

A

B

C

2

A

C

B

3

B

C

A

4

B

A

C

5

C

B

A

6

C

A

B

Top View

B

C

A

FLOW

MASTER

SLAVE

COMMON

COMMON

MASTER

SLAVE

MASTER

SLAVE

COMMON

MIXING

FLOW

FLOW

COMMON

SLAVE

MASTER

MASTER

SLAVE

COMMON

MASTER

COMMON

SLAVE

DIVERTING

FLOW

FLOW

FLOW

B

C

A

B

C

A

Arrangement 5

DIVERTING Flow Example

Arrangement 5

MIXING Flow Example

Master

Slave

Common

Master

Slave

Common

1

1

5

5

6

6

(Arrangements 2 and 4 not illustrated—

see actuator illustration below for Arrangement 3)

B

C

A

Actuator full CCW:
• Master valve closed
• Slave valve open
Actuator full CW:
• Master valve open
• Slave valve closed

Arrangement 3

Actuator

Mounting (2-Way and 3-Way)

VEF-56 3-Way Details

Maintenance

No routine maintenance is required. Careful installa-

tion ensures long-term reliability and performance.