KMC Controls VEB-56 Series User Manual
Installation guide, Caution
VEB-56 Series Valves
1
Installation Guide
Size
A
B
C
D
E
Weight (lb.)
4"
11.875
9
14.5
10.375
18
80
5"
13.875
10
15.5
12
18.875
95
6"
15.875
11
16.5
13.375
20
110
B
E
A
C
Diverting Flow Action:
Port '
AB
' to Port '
A
'—full CW; Port '
AB
' to '
B
'—full CCW
Full CW
A
B
AB
Mixing Flow Action:
Port '
A
' to Port '
AB
'—full CW; Port '
B
' to '
AB
'—full CCW
Full CCW
A
B
AB
Dimensions (Inches):
D
Installation Guide
3-Way, Mixing or Diverting, Flanged, Control Ball Valves
VEB-56 Series
Mounting 1
Wiring 2
Operation 2
Maintenance 2
Accessories/Repair Parts 2
More Information 2
Mounting
1. Clean the lines upstream from the valve. Remove
any debris (welding slag, pipe scale, or other
contaminants) larger than 1/16 inch (1.6 mm).
NOTE: If the system experiences large amounts
of debris, steps should be taken to keep
the system clean, such as 20 mesh strainer
installed upstream of the valve.
2. Align the valve assembly according to the system
flow requirements (see the illustration below).
3. The valve may be mounted on either vertical or
horizontal pipe lines. On horizontal lines, mount
the valve so the actuator is positioned upright
and over the valve. (Leave sufficient room on all
sides to service the actuator and valve.)
CAUTION
To prevent condensation from dripping onto the
actuator housing on horizontal lines, mount the
valve with the actuator in the upright position or, at
most, at a 45° angle.
4. Install approved flange gaskets (not supplied by
KMC Controls) and bolt the valve to the pipes.
5. Eliminate air from the system to keep the valves
full of fluid during operation.
UP (on
horizontal
lines)
CAUTION
Using mineral oil lubricants or other incompatible substances in
system fluids may damage EPDM rubber seals in valves. Before
using any lubricant or additive in a water or ethylene glycol
base, consult the substance manufacturer for compatibility with
EPDM (Ethylene Propylene Diene Monomer).