Rcc-1009/1109 switching/diverting, Rcc-1013 repeating, Rcc-1102 averaging – KMC Controls RCC-1100 Series User Manual
Page 2: Accessories, Maintenance, Important notices, Important notices 2, Caution

RCC-1000/1100 Series
2
Installation Guide
© 2011 KMC Controls, Inc.
100-019-01I
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
Important Notices
The material in this document is for information
purposes only. The contents and the product it
describes are subject to change without notice.
KMC Controls, Inc. makes no representations or
warranties with respect to this document. In no event
shall KMC Controls, Inc. be liable for any damages,
direct or incidental, arising out of or related to the
use of this document.
Maintenance
No routine maintenance is required. Each compo-
nent is designed for dependable, long-term reliabil-
ity, and performance. Careful installation will also
ensure long-term reliability and performance.
RCC-1009/1109 Switching/Diverting
Each unit is factory set to switch between 18 and 23
psi. This allows the unit to match most two-pressure
main air systems. This device is not “snap-acting” (it
must receive a positive pressure change at its signal
port to switch).
1. Apply air pressure to Port C.
2. Apply the lower switching signal to Port S.
3. With an accurate pressure gauge, check that the
pressure at Port NO is equal to the pressure at
Port C. If not, adjust the setpoint dial until the
pressures are equal and no pressure is detected at
Port NC.
4. Apply the higher switching pressure to Port S.
5. Check that the pressure at Port NC is equal to the
pressure at Port C. If not, adjust the setpoint dial
until the pressures are equal and no pressure is
detected at Port NO.
HMO-4511
Replacement mounting bracket
Accessories
The setpoint dial can be rotated within the body to adjust the switching point. One turn yields
approximately 6 psi change in the switching point. Each unit is factory-set to switch between
18 and 23 psi, which allows it to match most two-pressure main air systems. This device is not
“snap-acting” (it must receive a positive pressure change at its signal port to switch).
RCC-1013 Repeating
1. Apply main air pressure to Port M.
2. Connect Output to Port B.
3. Connect Input to Port S.
No calibration is required
.
Main air is Port M and output is Port B. The input signal to be repeated is connected to Port S.
RCC-1102 Averaging
1. Connect Main air to Port M, 20 psi with 30 psi
maximum.
2. Connect Output to Port B.
3. Connect the inputs for averaging to Port S1 and
S2.
No calibration is required.
Main air is Port M and output is Port B. Inputs to be averaged are applied to S1 and S2.
CAUTION
Pneumatic devices must be supplied with clean, dry
control air. Any other medium (e.g., oil or moisture
contamination) will cause the device to fail.