CCE-3000 Series

1

Installation Guide

Installation Guide

Pneumatic-Electric Relays, Single and Multi-Stage

CCE-3000 Series

Mounting

The CCE-3000 Series relays are not position sensitive

and may be mounted in any orientation.

Model CCE-3001

1. Surface mount using the two 3/16" diameter

holes.

2. Bulkhead mount using the 9/16-18 boss and nut.

Model CCE-3002/3003

1. Surface mount using the two 3/16" diameter

holes.

2. Bulkhead mount using two #6 self-threading

screws.

Mounting

1

Model CCE-3001

1

Model CCE-3002/3003 1

Connections and Wiring 1

Electrical

1

Air Supply

1

Adjustments and Calibration 2
Accessories

2

Maintenance

2

Specifications 2
Important Notices 2

CCE-3001

CCE-3003

Connections and Wiring

Electrical

Connections are made to 1/4" quick connect ter-

minals. Do not exceed the electrical ratings of the

switches (see

Specifications on page 2

).

1. Connect to the Common “C” and Normally Open

“NO” terminals if a fall in signal should break the

circuit.

2. Connect to the Common “C” and Normally

Closed “NC” terminal if a fall in signal should

make a circuit.

Air Supply

1. Using 1/4" (6 mm) OD polyethylene tubing,

connect the signal to the 3/16" (5 mm) inlet in the

bottom of the unit.

2. Limit the signal to 30 psig (207 kPa) max.

CAUTION

Pneumatic devices must be supplied with clean, dry
control air. Any other medium (e.g., oil or moisture
contamination) will cause the device to fail.