CTE-3016/3017/3026/3027

2

Installation Guide

© 2010 KMC Controls, Inc.

717-019-21B

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com; [email protected]

Accessories

HMO-4523

Capillary Clip (3 or 5 provided,

depending on length)

Important Notices

The material in this document is for information

purposes only. The contents and the product it

describes are subject to change without notice. KMC

Controls, Inc. makes no representations or warran-

ties with respect to this document. In no event shall

KMC Controls, Inc. be liable for any damages, direct

or incidental, arising out of or related to the use of

this document.

Specifications

Maintenance

No routine maintenance is required. Each compo-

nent is designed for dependable, long-term reliabil-

ity, and performance. Careful installation will also

ensure long-term reliability and performance.

Setpoint Adjustment

The setpoint is the temperature at which contacts

“11–14” and “21–24” open as the unit senses a fall in

temperature. To adjust the setpoint:
• Turn the range adjustment screw CW to decrease

the setpoint.

• Turn the range adjustment screw CCW to

increase the setpoint.

Testing

A manual test lever located under the cover (below

and to the left of the controller spring) allows the

unit to be manually actuated during system tests.

Actuation and Reset

Terminals 11 and 21 are “common” terminals, 14

and 24 are Normally Closed (above setpoint), and

12 and 22 are Normally Open (see the diagram

below). When the sensed temperature falls below

setpoint, connections “11–14” and “21–24” open and

connections “11–12” and “21–22” close. The switch

latches in this position until the sensed temperature

rises 5° F (3° C) above setpoint and the controller is

reset either (depending on the model) automatically

or manually by depressing the reset button located in

the top of the controller case.
The controller cannot be manually reset until the

sensed temperature is at least 5° F (3° C) above the

setpoint.

Range

34° to 70° F (1.1° to 21° C)

Differential

4.5° F fixed (2.5° C)

Switch Action

DPDT

Element

3/32" (2.4 mm) diameter, 6-foot

(183 cm) or 20-foot (607 cm)

length, vapor-filled, tin-plated

copper capillary, maximum

temperature 300° F (149° C)

Electrical Ratings

Inductive

14 FLA (Full Load Amperes)

@ 120 VAC, 12 FLA @ 240 VAC

84 LRA (Locked Rotor

Amperes) @ 120 VAC, 72 LRA

@ 240 VAC

3/4 HP @ 120 VAC, 2 HP @ 240

VAC

Pilot Duty

720 VA max. @ 120 to 600 VAC,

144 VA max. @ 24 VAC

Approvals

CUL US Listed, CE Compliant,

RoHs compliant

Weight

1.2 lbs. (0.54 kg)

Materials

Plated steel case, plastic cover

Mounting

Surface mount with capillary

installed in horizontal serpen-

tine pattern

Temperature Limits

Operating

–60 to 160° F (–51 to 71° C)

Shipping

–60 to 160° F (–51 to 71° C)

NOTE: See the CTE-3016/3017/3026/3027 Data

Sheet (717-035-21) for more information.

21

(Common)

22 (NO)

24 (NC)

(Connections Shown in Above-Setpoint, NC, Unactuated Position)

11

(Common)

12 (NO, Closes

on Low Temp.)

14 (NC, Opens

on Low Temp.)