Troubleshooting, Maintenance, Important notices – KMC Controls REE-4001 User Manual
Page 2

© 2010 KMC Controls, Inc.
809-019-04D
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com; [email protected]
Maintenance
No routine maintenance is required, however protec-
tion from extremes of humidity and dirt is recom-
mended. Careful installation will also ensure long
term reliability and performance.
NOTE: For more information about the CEP-4000/
CTE-1004 example, see the CEP-4000
Series VAV Flow Controllers-Actuators
Application Guide.
NOT
E: The “C” terminal does NOT denote
Common/Neutral. “C” is the phase side
of the 24 VAC (and is also the side the
contactors have in “common”). “9” is the
neutral side. Triac
stages 1 through 3 are
for 24 VAC loads only.
NOTE: “T” input
is 0 to
6 VDC.
(See the
Thermostat
Signal
chart.)
Stage
Status
Normal Triac Voltage (Approximate, and With Load)
Across
Load (Terminal C/
Phase to Terminal 1, 2, or 3)
Across
Triac (Terminal 9/
Neutral to Terminal 1, 2, or 3)
On
24 VAC
1 VAC
Off
0 VAC
24 VAC
Troubleshooting
• Check the wiring.
• Check the voltage from the thermostat/controller
(measured from Terminal T to Terminal 9/Neu-
tral). (See the chart on the previous page.)
• Check the voltage across the triac and load. (See
the chart below.)
Important Notices
The material in this document is for information
purposes only. The contents and the product it
describes are subject to change without notice. KMC
Controls, Inc. makes no representations or warran-
ties with respect to this document. In no event shall
KMC Controls, Inc. be liable for any damages, direct
or incidental, arising out of or related to the use of
this document.
St
ages
24 V
AC
GND
(–)
OUT
(+)
(Alternate Direct
Control from an
Analog or DDC
Controller)