Troubleshooting, Maintenance, Important notices – KMC Controls REE-4001 User Manual

Page 2

background image

© 2010 KMC Controls, Inc.

809-019-04D

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com; [email protected]

Maintenance

No routine maintenance is required, however protec-

tion from extremes of humidity and dirt is recom-

mended. Careful installation will also ensure long

term reliability and performance.

NOTE: For more information about the CEP-4000/

CTE-1004 example, see the CEP-4000

Series VAV Flow Controllers-Actuators

Application Guide.

NOT

E: The “C” terminal does NOT denote

Common/Neutral. “C” is the phase side

of the 24 VAC (and is also the side the

contactors have in “common”). “9” is the

neutral side. Triac

stages 1 through 3 are

for 24 VAC loads only.

NOTE: “T” input

is 0 to

6 VDC.

(See the

Thermostat

Signal

chart.)

Stage

Status

Normal Triac Voltage (Approximate, and With Load)

Across

Load (Terminal C/

Phase to Terminal 1, 2, or 3)

Across

Triac (Terminal 9/

Neutral to Terminal 1, 2, or 3)

On

24 VAC

1 VAC

Off

0 VAC

24 VAC

Troubleshooting

• Check the wiring.
• Check the voltage from the thermostat/controller

(measured from Terminal T to Terminal 9/Neu-

tral). (See the chart on the previous page.)

• Check the voltage across the triac and load. (See

the chart below.)

Important Notices

The material in this document is for information

purposes only. The contents and the product it

describes are subject to change without notice. KMC

Controls, Inc. makes no representations or warran-

ties with respect to this document. In no event shall

KMC Controls, Inc. be liable for any damages, direct

or incidental, arising out of or related to the use of

this document.

St

ages

24 V

AC

GND

(–)

OUT

(+)

(Alternate Direct

Control from an

Analog or DDC

Controller)