REE-2101/2102 Solid-State Triac Relays
Installation Guide
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
Connections and Wiring
1. Remove the “AUTO-MANUAL-OFF” jumper and
save.
2. Wire the input(s) common ground to (–) “GND”
of the Input terminal block.
3. Wire the individual (+ 10–14 VDC) input(s) to the
appropriate terminal(s) of the Input block.
NOTE: If the “MANUAL” mode is to be used,
wire power (+ 10–14 VDC) to the “PWR”
terminal of the Input terminal block. This
must have the same reference (–) ground
as the inputs.
4. Wire the individual output(s) to the appropriate
terminals of the Output terminal block.
NOTE: Triacs are for switching AC only. The triac
output must be in series with the load
and transformer output. Output rating is
up to 1 A at 30 VAC. See the data sheet for
additional specifications.
5. Reinsert the jumper in the “AUTO” position.