REE-2101/2102 Solid-State Triac Relays

Installation Guide

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com

[email protected]

Connections and Wiring

1. Remove the “AUTO-MANUAL-OFF” jumper and

save.

2. Wire the input(s) common ground to (–) “GND”

of the Input terminal block.

3. Wire the individual (+ 10–14 VDC) input(s) to the

appropriate terminal(s) of the Input block.

NOTE: If the “MANUAL” mode is to be used,

wire power (+ 10–14 VDC) to the “PWR”

terminal of the Input terminal block. This

must have the same reference (–) ground

as the inputs.

4. Wire the individual output(s) to the appropriate

terminals of the Output terminal block.

NOTE: Triacs are for switching AC only. The triac

output must be in series with the load

and transformer output. Output rating is

up to 1 A at 30 VAC. See the data sheet for

additional specifications.

5. Reinsert the jumper in the “AUTO” position.