Connections and Wiring
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
1. Remove and save the AUTO-MANUAL-OFF
jumper.
2. Wire the input(s) common ground to “GND” of
the INPUT terminal block.
3. Wire the individual (6–40 VDC or 24 VAC)
input(s) to the appropriate terminal(s) of the
INPUT block.
*NOTE: Putting the jumper into the “MANUAL”
position turns on the triac relay (when no
triggering voltage is present on the input).
If “MANUAL” mode is to be used, wire
power (+ 6–40 VDC or 24 VAC) to the
“POWER” terminal of the INPUT terminal
block. This must have the same reference
(–) ground as the inputs.
4. Wire the individual output(s) to the appropriate
terminals of the OUTPUT terminal block.
NOTE: Triacs are for switching
AC only. Output
rating is up to 5 A at 280 VAC. See the data
sheet for additional specifications.
5. The triac output must be in series with the load
and transformer output.
6. Replace the jumper to the “AUTO” position.
*NOTE: The jack on the board for a plug-in
transformer was discontinued on units built
after May 2013. Connect auxiliary (manual
override) power to the Power and Ground
terminals instead. If an older unit that uses
a plug-in transformer is being replaced,
cut the plug off the transformer cable and
connect the wires to the Power (+) and
Ground (–) terminals.
© 2014 KMC Controls, Inc.
872-019-01E
*
Important Notices
The material in this document is for information
purposes only. The contents and the product it
describes are subject to change without notice. KMC
makes no representations or warranties with respect
to this document. In no event shall KMC be liable for
any damages, direct or incidental, arising out of or
related to the use of this document.