Connections and Wiring

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com

[email protected]

1. Remove and save the AUTO-MANUAL-OFF

jumper.

2. Wire the input(s) common ground to “GND” of

the INPUT terminal block.

3. Wire the individual (6–40 VDC or 24 VAC)

input(s) to the appropriate terminal(s) of the

INPUT block.

*NOTE: Putting the jumper into the “MANUAL”

position turns on the triac relay (when no

triggering voltage is present on the input).

If “MANUAL” mode is to be used, wire

power (+ 6–40 VDC or 24 VAC) to the

“POWER” terminal of the INPUT terminal

block. This must have the same reference

(–) ground as the inputs.

4. Wire the individual output(s) to the appropriate

terminals of the OUTPUT terminal block.

NOTE: Triacs are for switching

AC only. Output

rating is up to 5 A at 280 VAC. See the data

sheet for additional specifications.

5. The triac output must be in series with the load

and transformer output.

6. Replace the jumper to the “AUTO” position.

*NOTE: The jack on the board for a plug-in

transformer was discontinued on units built

after May 2013. Connect auxiliary (manual

override) power to the Power and Ground

terminals instead. If an older unit that uses

a plug-in transformer is being replaced,

cut the plug off the transformer cable and

connect the wires to the Power (+) and

Ground (–) terminals.

© 2014 KMC Controls, Inc.

872-019-01E

*

Important Notices

The material in this document is for information

purposes only. The contents and the product it

describes are subject to change without notice. KMC

makes no representations or warranties with respect

to this document. In no event shall KMC be liable for

any damages, direct or incidental, arising out of or

related to the use of this document.

This manual is related to the following products: