Up and Down Buttons
To view the “High Temp” recorded by the cooling
unit, press the “Up” button once.
To view the “Low Temp” recorded by the cooling
unit, press the “Down” button once.
To reset the “High Temp” or “Low Temp”, press
the “Set” button for three seconds while “Hi” or
“Lo” is displayed. “RST” will blink three times to
indicate confirmation.
Set Button
The cooling unit is factory preset with a Minimum
Set Point of 58°F and a Temperature Differential
of 4°F. This means that the cooling unit will turn
on when the display rises above 62°F (58°F +
4°F), and turn off when the display falls below
58°F. In this example, the average temperature
inside the cellar will be 60°F.
To view the Minimum Set Point, press the “Set”
button for one second.
To change the Minimum Set Point,
Press the “Set” button for three seconds
until °F” blinks
Press “Up” or “Down” button
Press “Set” button to confirm
The “Set” temperature will blink three times to
indicate confirmation
The recommended Minimum Set Point range is
53 - 60°F. To change the Temperature
Differential, see “Advanced Operation” later in
this chapter.