Humidifier (optional):
Recommended for installations where the ambient humidity is insufficient to maintain 50
to 70%RH inside the cellar. The humidity control is remote mounted with 10ft of
interconnecting wire inside the cellar. Refer to separate manual for detailed installation
and operating instructions for the humidifier and humidity controller.

Heating (optional):
The air handler can be configured with an electric air heater for installations where the
cellar may drop below the desired set point. The controller is factory programmed to
automatically activate the heater and the evaporator fan when the cellar temperature is
below the desired set point (parameter SET) minus the temperature differential
(parameter HY). For example, if the set point (Set) is 55 , and the differential (HY) is 4,
the heater will energize when the cellar temperature reaches 55 minus 4 = 51°F, and
turn off when the cellar reaches 55°F. Refrigeration will be activated when the cellar
temperature reaches 55 plus 4 = 59°F. If a tighter range is required, the HY should be
set to "2" for the heating season. If an optional bottle probe is used to maintain the
cellar temperature, the factory setting for HY is "1", and adjustment is not required.
There are two heating element options: 900W and 1800W. An application chart is
shown below to assist in selecting the correct wattage. For the majority of applications,
the 900W heater is recommended.

900W Heater Specifications

1800W Heater Specifications

Power Consumption

7.8 Amps @ 115V / 60Hz

Power Consumption

15.7 Amps @ 115V / 60Hz

Fan Speed

Total BTUH (including fan)

Fan Speed

Total BTUH (including fan)

High

4702

High

7774

Medium

4346

Medium

7417

Low

4218

Low

7290

Ambient Temperature / Insulation Type

Cellar

Dimensions

45°F

30°F

15°F

0°F

Nominal Size

(cuft)

R-12

R-19

R-30

R-12

R-19

R-30

R-12

R-19

R-30

R-12

R-19

R-30

1000

630

511

439

1574

1278

1098

2519

2045

1757

3464

2812

2416

1250

746

614

534

1864

1535

1335

2983

2456

2136

4102

3377

2937

1500

866

721

633

2164

1802

1582

3463

2883

2531

4761

3965

3481

1750

968

812

718

2419

2031

1795

3871

3250

2872

5323

4468

3949

2000

1103

934

832

2757

2336

2080

4412

3738

3328

6066

5139

4576

2250

1188

1011

904

2969

2528

2260

4751

4045

3617

6533

5562

4973

2500

1306

1119

1005

3264

2797

2513

5223

4475

4021

7182

6153

5528

2725

1398

1203

1085

3495

3007

2711

5591

4812

4338

7688

6616

5965

3025

1525

1320

1195

3813

3299

2987

6100

5279

4780

8388

7258

6572

Assumes all walls and ceiling are exposed to ambient temperature indicated. Floor is slab on grade.

= Shaded areas require 1800W heater option

Cellar Heating Load (BTUH) for 55°F Average Cellar Temperature

Humidification may be required to maintain cellar humidity levels >50%RH