Humidifier (optional):
Recommended for installations where the ambient humidity is insufficient to maintain 50
to 70%RH inside the cellar. The humidity control is remote mounted with 10ft of
interconnecting wire inside the cellar. Refer to separate manual for detailed installation
and operating instructions for the humidifier and humidity controller.
Heating (optional):
The air handler can be configured with an electric air heater for installations where the
cellar may drop below the desired set point. The controller is factory programmed to
automatically activate the heater and the evaporator fan when the cellar temperature is
below the desired set point (parameter SET) minus the temperature differential
(parameter HY). For example, if the set point (Set) is 55 , and the differential (HY) is 4,
the heater will energize when the cellar temperature reaches 55 minus 4 = 51°F, and
turn off when the cellar reaches 55°F. Refrigeration will be activated when the cellar
temperature reaches 55 plus 4 = 59°F. If a tighter range is required, the HY should be
set to "2" for the heating season. If an optional bottle probe is used to maintain the
cellar temperature, the factory setting for HY is "1", and adjustment is not required.
There are two heating element options: 900W and 1800W. An application chart is
shown below to assist in selecting the correct wattage. For the majority of applications,
the 900W heater is recommended.
900W Heater Specifications
1800W Heater Specifications
Power Consumption
7.8 Amps @ 115V / 60Hz
Power Consumption
15.7 Amps @ 115V / 60Hz
Fan Speed
Total BTUH (including fan)
Fan Speed
Total BTUH (including fan)
High
4702
High
7774
Medium
4346
Medium
7417
Low
4218
Low
7290
Ambient Temperature / Insulation Type
Cellar
Dimensions
45°F
30°F
15°F
0°F
Nominal Size
(cuft)
R-12
R-19
R-30
R-12
R-19
R-30
R-12
R-19
R-30
R-12
R-19
R-30
1000
630
511
439
1574
1278
1098
2519
2045
1757
3464
2812
2416
1250
746
614
534
1864
1535
1335
2983
2456
2136
4102
3377
2937
1500
866
721
633
2164
1802
1582
3463
2883
2531
4761
3965
3481
1750
968
812
718
2419
2031
1795
3871
3250
2872
5323
4468
3949
2000
1103
934
832
2757
2336
2080
4412
3738
3328
6066
5139
4576
2250
1188
1011
904
2969
2528
2260
4751
4045
3617
6533
5562
4973
2500
1306
1119
1005
3264
2797
2513
5223
4475
4021
7182
6153
5528
2725
1398
1203
1085
3495
3007
2711
5591
4812
4338
7688
6616
5965
3025
1525
1320
1195
3813
3299
2987
6100
5279
4780
8388
7258
6572
Assumes all walls and ceiling are exposed to ambient temperature indicated. Floor is slab on grade.
= Shaded areas require 1800W heater option
Cellar Heating Load (BTUH) for 55°F Average Cellar Temperature
Humidification may be required to maintain cellar humidity levels >50%RH