beautypg.com

CellarPro AIR HANDLER 6500 HORIZONTAL, 7090 User Manual

Page 23

background image

23

Split System R-134a Charge Guidelines

Weigh in the R-134a refrigerant via the liquid service valve according to the chart below:

System R-134a Charge Guidelines

Actual Line

Length

System Charge (lbs) by Split System Model

(ft)

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

AH6500S

3.72 3.92 4.12 4.33 4.53 4.74 4.94 5.15 5.35 5.55 5.76 5.96 6.17 6.37 6.57 6.78 6.98 7.18

AH8500S

3.72 3.92 4.13 4.33 4.53 4.74 4.94 5.15 5.44 5.66 5.87 6.09 6.30 6.51 6.73 6.94 7.16 7.37

Note:
1)

Actual charge may vary - follow charging instructions detailed under Item 6 in the section titled

Evacuation, Leak Detection, and Charging (above).
2)

Lines sized according to Line Sizing Chart assuming actual line length plus 10 equivalent feet for

fitting losses

Summary

Keep in mind the following guidelines when selecting your wine cooling unit from
CellarPro:

 If the cellar is too large for the cooling unit, the cooling unit will be unable to

maintain proper, even temperatures inside the cellar.

 Without proper insulation and an airtight environment, the cooling unit effectively

will become a de-humidifier and potentially will produce buckets of water.

 Without access to cool air, either because of improper ventilation or because the

environments is too hot, the cooling unit will be unable to maintain proper
temperatures inside the cellar.

 When the cooling unit will be exposed to temperatures below 40°F, a

compressor heater must be added to protect the compressor.

Under any of the above conditions, the unit’s internal components may become
damaged, the expected useful life of the wine cooling unit may be adversely
affected, and the product’s warranty may become null and void.