Dv power vent system, Venting up – Vermont Casting 7PDVS User Manual

Page 9

background image

9

DV Power Vent System

10003262

L

6

L

7

L

5

L

2

L

4

L

3

L

1

In the above example there are:

4 times 90 degrees elbows = 360 degrees

2 times 45 degrees elbows = 90 degrees

Total elbow degrees = 450 degrees

Installation is OK

A - Maximum 40FT of straight pipe.

B - Minimum 10FT of straight pipe for units up to 33,000BTU/h,
Minimum 15FT of straight pipe for units from 33,000BTU/h
to 40,000BTU/h.

C - Maximum 6FT of straight pipe.

A = L

1

+L

2

+L

3

+L

4

+L

5

+L

6

+L

7

B = L

1

+L

2

+L

3

+L

4

+L

5

C = L

6

+L

7

Venting Up: