beautypg.com

Carrier 38BRC User Manual

Page 4

background image

Relieve pressure and recover all refrigerant before system
repair or final unit disposal to avoid personal injury or death.
Use all service ports and open all flow control devices,
including solenoid valves.

SEQUENCE OF OPERATION

Turn on power to indoor and outdoor units. Transformer is
energized.

On a call for cooling, thermostat makes circuits R-Y and R-G. On
three phase models with scroll compressors, the units are equipped
with a phase monitor to detect if the incoming power is correctly
phased for compressor operation. (See Fig. 4 and Table 2.) If the
phasing is correct, circuit R-Y energizes contactor, starting out-
door fan motor and compressor circuit. R-G energizes indoor unit
blower relay, starting indoor blower motor on high speed.

NOTE:

If the phasing is incorrect, the contactor will not be

energized. To correct the phasing, interchange any two of the three
power connections on the field side.

When thermostat is satisfied, its contacts open, de-energizing
contactor and blower relay. Compressor and motors stop.

If indoor unit is equipped with an off-delay circuit, the indoor
blower can run up to an additional 120 sec to increase system
efficiency.

Step 11—Check Charge

UNIT CHARGE

Factory charge is shown on unit rating plate. Charge procedure is
shown on wiring/charging label located on unit.

Compressor damage may occur if system is overcharged.

Do not vent refrigerant to atmosphere. Recover during system
repair or final unit disposal.

CARE AND MAINTENANCE

For continuing high performance, and to minimize possible
equipment failure, it is essential that periodic maintenance be

performed on this equipment. Consult your servicing contractor or
User’s Manual for proper frequency of maintenance. Frequency of
maintenance may vary depending upon geographic areas, such as
costal applications.

Leave User’s Manual with homeowner. Explain system operation
and maintenance procedures outlined in manual.

Fig. 4—3 Phase Monitor Control

A00010

Table 2—Phase Monitor LED Indicators

LED

STATUS

OFF

No call for compressor operation

FLASHING

Reversed phase

ON

Normal

4

This manual is related to the following products: