beautypg.com

Carrier 38BRC User Manual

Page 2

background image

Step 4—Operating Ambients (Outdoor Temperatures)

The minimum outdoor operating ambient in cooling mode is 55°F,
and the maximum outdoor operating ambient in cooling mode is
125°F.

Step 5—Replace Indoor AccuRater® Piston, If Required

Check indoor coil piston to see if it matches the required piston
shown on outdoor unit rating plate. If it does not match, replace
indoor coil piston with piston shipped with outdoor unit. The
piston shipped with outdoor unit is correct for any approved indoor
coil combination.

Step 6—Make Refrigerant Tubing Connections

Outdoor units may be connected to indoor sections using accessory
tubing package or field-supplied refrigerant grade tubing of correct
size and condition. For tubing requirements beyond 50 ft, consult
Application Guideline and Service Manual—Air Conditioners and
Heat Pumps Using R-22 Refrigerant. Connect tubing to fittings on
outdoor unit vapor and liquid service lines. (See Table 1.)

If refrigerant tubes or indoor coil is exposed to atmospheric
conditions for longer than 5 minutes, it must be evacuated to 500
microns to eliminate contamination and moisture in system.

OUTDOOR UNIT CONNECTED TO FACTORY-APPROVED
INDOOR UNIT

Outdoor unit contains correct system refrigerant charge for opera-
tion with indoor unit of same size when connected by 15 ft of
field-supplied or factory accessory tubing. Check refrigerant
charge for maximum efficiency. (See Procedure 11–Check
Charge.)

To avoid valve damage while brazing, service valves must be
wrapped with a heat-sinking material such as a wet cloth.

SWEAT CONNECTION

Use refrigerant grade tubing. Service valves are closed from
factory and ready for brazing. After wrapping service valve with a

Fig. 1—Connecting Tubing Installation

A94028

INSULATION

VAPOR TUBE

LIQUID TUBE

OUTDOOR WALL

INDOOR WALL

LIQUID TUBE

VAPOR TUBE

INSULATION

CAULK

Avoid contact between tubing and structure

NOTE:

THROUGH THE WALL

HANGER STRAP

(AROUND VAPOR

TUBE ONLY)

JOIST

1

MIN.

SUSPENSION

Fig. 2—Mounting Unit to Pad

Dimensions (In.)

UNIT BASE

DIMENSIONS

TIEDOWN KNOCKOUT LOCATIONS

A

B

C

18 X 18

3

15

10-3/16

22-1/2 X 22-1/2

3-11/16

18-1/8

14-3/8

30 X 30

6-1/2

23-1/2

20

A94199

C

B

A

3

8

D. (9.53) TIEDOWN

KNOCKOUTS (2) PLACES

2

This manual is related to the following products: