APPENDIX C:

Requirements for Installation and Use Within New York City Fire Department Jurisdiction

Owners and installers within NYCFD jurisdiction are required to meet the following guidelines
concerning the installation and use of VJ-Series design bulk tanks.


• The installation and use of the vessel must comply with all applicable New York City Codes,

Rules, and Regulations.


• After installation, the vessel shall not be filled until the required New York City Fire Department

storage permit has been issued.


• The owner / installer shall be in compliance with all of the manufacturer’s installation and

maintenance procedures and limitations.


• The liquid level gauge is to be marked to indicate the maximum permissible fill level for the

respective gas being utilized.


• The vessel fill capacity shall be limited to comply with CGA-341 (Standard for Insulated Cargo

Tank Specification for Cryogenic Liquids).


• The vessel is for outdoor use only, will be placed in areas acceptable to NYCFD, and must be

protected from vandalism.


• Changes in ownership or owner’s name must be reported to NYCFD in writing.

WARNING: Failure to comply with the conditions of Certificate of Approval #4969 can

be the basis for being subjected to enforcement action that can include fines

and imprisonment.