beautypg.com

Half duplex mode, Multi-drop slave mode, Tri-state control – Connect Tech Blue Heat/PCI PCI Serial Communications User Manual

Page 36

background image

Blue Heat/PCI User’s Manual, Connect Tech Inc.

Revision 0.11

36

Half Duplex Mode
In this mode the TxD line driver is enabled only when data is transmitted and RxD is disabled
when data is being transmitted. This mode is typically used in either point to point "2 wire"
connections OR in multi-drop "2 wire" bus connections. To enable this mode for a port you
must jumper positions 7 and 8 on the appropriate jumper blocks JA, JB, JC, JD. These jumpers
short TxD – to RxD – and TxD + to RxD +.

Figure 6

depicts the locations of jumper blocks JA,

JB, JC and JD.

Example
The following example shows the settings on JA, JB, JC and JD
where the RS-422/485 port 1 is set half duplex, the RS-422/485
port 2 is set for half duplex; RS-422/485 port 3 is set for full
duplex or multi-drop slave, and the RS-422/485 port 4 is set for
full duplex or multi-drop slave.

JD1

JB

JC

JD2

JD3

JD4

JD5

JD6

JD7

JD8

JD JA

COM4

JC1

JC2

JC3

JC4

JC5

JC6

JC7

JC8

COM3

JB1

JB2

JB3

JB4

JB5

JB6

JB7

JB8

COM2

JA1

JA2

JA3

JA4

JA5

JA6

JA7

JA8

COM1

RTS ± TERM

TXD ± TERM

CTS ± BIAS

CTS ± BIAS

RXD ± BIAS

RXD ± BIAS

Insert for 1/2 D

Insert for 1/2 D


Technical Notes:
If you wish to set a specific port for half duplex, you must
jumper both positions 7 and 8 on the appropriate jumper block.
For RS-232 ports do not jumper any positions on the
appropriate JA, JB, JC and JD jumper block.

Multi-drop Slave Mode
In this mode the TxD line driver is enabled only when data is transmitted and RxD is enabled all
the time. This mode is typically used in multi-drop "4 wire" connections.

Tri-state Control
The Blue Heat/PCI Opto adapters allow you to tri-state the line drivers on power up. To tri-state
the drivers on power up please make certain there is no jumper installed across the pins on
jumper block JI. Please refer to

Figure 6

for the location of J1.

Example
The following example shows the settings on J1 to tri-state the
transceivers upon power up of the Blue Heat/PCI Opto
adapter.

J1

RS485 TX Power up
ON = ENABLED
OFF = DISABLED

1.