Troubleshooting, Nvb series b-vent gas fireplace – Vermont Casting NVBR36 User Manual

Page 17

background image

17

NVB Series B-Vent Gas Fireplace

7412950

Troubleshooting

FP396

Gas Supply On

• Supply Line Hooked up

• Shutoff Valve Open

NO

NO

NO

NO

• Lockout has engaged. Wait 60

seconds and try again.

• Piezo not tight enough for good

ground.

• For spark at electrode while

depressing Piezo (Red Button)

1/8" gap to pilot hood needed.

• All wiring connections

• Replace Piezo Ignitor

• Thermodisk

• For Air in the lines

• Thermopile needs a minimum

325mV. Adjust pilot flame height.

• All wiring connections

• Replace Thermopile

• Thermocouple needs a minimum

of 14mV.

• Defective valve. Turn to pilot,

meter should read greater than

100mV.

• Thermodisk

Pilot Lights with

Piezo Ignitor

YES

YES

YES

YES

Pilot Stays Lit

Pilot Lights Main

Burner

System OK

START

CHECK

• Wall switch is not turned on.

Watch for grounded wires!

• Thermopile needs a minimum

325mV

• Plugged burner orifice

FP396

NVC-standing pilot troubleshooting

5/6/98

Nova SIT 820 Standing Pilot