Dell UPS 3750R User Manual
Page 75
75
MIB Objects
|
Table 15. Product Physical Group Variables (continued)
Trap Name, Description, and Relative XML Object Path
Trap Level
Trap
trapBatteryTestDone (physical BatteryTestStatus)
Battery test done
Variable: physicalBatteryTestStatusUPS.BatterySystem.Battery.Test ? 5
62
1
trapBatteryNeedReplacement
Battery test failed, battery needs to be replaced
UPS.PowerSummary.PresentStatus.NeedReplacement = 1
63
3
trapBatteryReplacementDone
Battery replacement done
UPS.PowerSummary.PresentStatus.NeedReplacement = 0
64
1
trapFanFailure
Fan failure
UPS.PowerSummary.PresentStatus.FanFailure = 1
65
3
trapFanOk
Fan ok
UPS.PowerSummary.PresentStatus.FanFailure = 0
66
1
trapSiteWiringFault
Site wiring fault
UPS.PowerConverter.Input[1].PresentStatus.WiringFault = 1
67
3
trapSiteWiringOk
Site wiring ok
UPS.PowerConverter.Input[1].PresentStatus.WiringFault = 0
68
1
trapBatteryDisconnected
Batteries disconnected
UPS.BatterySystem.Battery.PresentStatus.Present = 0
69
3
trapBatteryConnected
Batteries connected
UPS.BatterySystem.Battery.PresentStatus.Present = 1
70
1
trapUPSOff
UPS off
UPS.PowerSummary.PresentStatus.Good = 0
71
2
trapUPSOn
UPS on
UPS.PowerSummary.PresentStatus.Good = 1
72