Traps – Dell UPS 3750R User Manual
Page 69
69
MIB Objects
|
Table 14. Product Physical Group Variables (continued)
Variable Name and Description
Variable
Unit
Variable
Type
OID
physicalLoadSegment2ShutdownAfterDelay
Number of seconds remaining until Load Segment 2 switches off. -1 if no shutdown
countdown is in effect.
UPS.OutletSystem.Outlet[3].DelayBeforeShutdown
6.3
Integer
Seconds
physicalLoadSegment2StartupAfterDelay
Number of seconds remaining until Load Segment 2 switches on. -1 if no startup
countdown is in effect.
UPS.OutletSystem.Outlet[3].DelayBeforeStartup
6.4
Integer
Seconds
Traps
Traps are sent on status transition (when an alarm appears or disappears). Traps are composed of three
levels and can be filtered:
S
Informational
S
Warning
S
Critical
Trap OID is: 1.3.6.1.4.1.674.10902.2.140 (see Table 15).
Table 15. Product Physical Group Variables
Trap Name, Description, and Relative XML Object Path
Trap
Trap Level
trapInverterOverVoltage
Inverter AC over voltage (applies only to double-conversion models)
UPS.PowerConverter.Inverter.PresentStatus.VoltageTooHigh = 1
1
2
trapInverterOverVoltageOk
Inverter AC over voltage ok
UPS.PowerConverter.Inverter.PresentStatus.VoltageTooHigh = 0
2
1
trapInverterUnderVoltage
Inverter AC under voltage (applies only to double-conversion models)
UPS.PowerConverter.Inverter.PresentStatus.VoltageTooLow = 1
3
2
trapInverterUnderVoltageOk
Inverter AC under voltage ok
UPS.PowerConverter.Inverter.PresentStatus.VoltageTooLow = 0
4
1