Dell UPS 3750R User Manual
Page 72
72
|
MIB Objects
Table 15. Product Physical Group Variables (continued)
Trap Name, Description, and Relative XML Object Path
Trap Level
Trap
trapPosDCLinkUnderVoltage
Positive DC link under voltage (applies only to double-conversion models)
UPS.PowerConverter.Rectifier.PresentStatus.LowPositiveDCBusVoltage = 1
27
2
trapPosDCLinkUnderVoltageOk
Positive DC link under voltage ok
UPS.PowerConverter.Rectifier.PresentStatus.LowPositiveDCBusVoltage = 0
28
1
trapNegDCLinkOverVoltage
Negative DC link over voltage (applies only to double-conversion models)
UPS.PowerConverter.Rectifier.PresentStatus.HighNegativeDCBusVoltage = 1
29
2
trapNegDCLinkOverVoltageOk
Negative DC link over voltage ok
UPS.PowerConverter.Rectifier.PresentStatus.HighNegativeDCBusVoltage = 0
30
1
trapNegDCLinkUnderVoltage
Negative DC link under voltage (applies only to double-conversion models)
UPS.PowerConverter.Rectifier.PresentStatus.LowNegativeDCBusVoltage = 1
31
2
trapNegDCLinkUnderVoltageOk
Negative DC link under voltage ok
UPS.PowerConverter.Rectifier.PresentStatus.LowNegativeDCBusVoltage = 0
32
1
trapRectifierFault
Rectifier fault (applies only to double-conversion models)
UPS.PowerConverter.Rectifier.PresentStatus.InternalFailure = 1
33
3
trapRectifierOk
Rectifier ok
UPS.PowerConverter.Rectifier.PresentStatus.InternalFailure = 0
34
1
trapInverterFault
Inverter fault (applies only to double-conversion models)
UPS.PowerConverter.Inverter.PresentStatus.InternalFailure = 1
35
3
trapInverterOk
Inverter ok
UPS.PowerConverter.Inverter.PresentStatus.InternalFailure = 0
36
1
trapChargerFailure
Charger failure
UPS.BatterySystem.Charger.PresentStatus.InternalFailure = 1
37
3