Carrier 50PG03-16 User Manual
Page 27

27
Table 2 — Electrical Data — Units With Optional Powered Convenience Outlet (cont)
UNIT
50PG
NOMINAL
POWER
SUPPLY
VOLTS-PH-HZ
VOLTAGE
RANGE
COMPRESSOR
OFM
FLA
IFM
FLA
POWER
EXHAUST
FLA
IFM
TYPE
ELECTRIC
HEAT
POWER
SUPPLY
CRSINGLE
PART
NO.
(NOTE3)
DISCONNECT
SIZE
WIRING
FIG.
NO.
MIN
MAX
RLA
LRA
CRHEATER
PART
NO.
FLA
NOMINAL
KW*
MCA
MOCP†
FLA
LRA
08
(cont)
575-3-60
518
632
6.4
30.0
0.8
2.0
Ċ
Low
Ċ
Ċ
Ċ
20.1
20
Ċ
21
86
Ċ
239A00
13.9
15.0
22.0
25
030A00
21
86
15
240A00
23.1
25.0
33.5
35
030A00
31
86
15
241A00
32.3
35.0
45.1
50
030A00
41
86
15
242A00
37.0
40.0
50.9
60
030A00
47
86
15
High
Ċ
Ċ
Ċ
20.6
20
Ċ
22
104
Ċ
239A00
13.9
15.0
23.0
25
030A00
22
104
15
240A00
23.1
25.0
34.5
35
030A00
32
104
15
241A00
32.3
35.0
46.1
50
030A00
42
104
15
242A00
37.0
40.0
51.9
60
030A00
48
104
15
575-3-60
518
632
6.4
30.0
0.8
2.8
3.0
Low
Ċ
Ċ
Ċ
19.9
25
Ċ
21
88
Ċ
239A00
13.9
15.0
25.7
30
030A00
24
88
15
240A00
23.1
25.0
37.3
40
030A00
34
88
15
241A00
32.3
35.0
48.8
50
030A00
45
88
15
242A00
37.0
40.0
54.6
60
030A00
50
88
15
High
Ċ
Ċ
Ċ
20.7
25
Ċ
22
100
Ċ
239A00
13.9
15.0
26.7
30
030A00
25
100
15
240A00
23.1
25.0
38.3
40
030A00
35
100
15
241A00
32.3
35.0
49.8
50
030A00
46
100
15
242A00
37.0
40.0
55.6
60
030A00
51
100
15
09
208/230-3-60
187
253
16.0
91
1.5
5.2
Ċ
Low
Ċ
Ċ
Ċ/Ċ
49.1/ 49.1
60/ 60
Ċ
52/ 52
223/223
Ċ
225A00
20.0/23.1
7.5/10.0
49.1/ 49.1
60/ 60
030A00
52/ 52
223/223
15
226A00
30.0/34.6 11.3/15.0
50.0/ 55.2
60/ 60
030A00
52/ 52
223/223
15
227A00
50.0/57.7 18.8/25.0
75.1/ 84.1
80/ 90
031A00
69/ 78
223/223
16
228A00
70.0/80.8 26.3/35.0
100.1/113.0
110/125
031A00
92/104
223/223
17
229A00
80.0/92.4 30.0/40.0
112.6/127.4
125/150
031A00
104/118
223/223
17
10.2
High
Ċ
Ċ
Ċ/Ċ
54.1/ 54.1
60/ 60
Ċ
58/ 58
266/266
Ċ
225A00
20.0/23.1
7.5/10.0
54.1/ 54.1
60/ 60
031A00
58/ 58
266/266
15
226A00
30.0/34.6 11.3/15.0
56.3/ 61.5
60/ 70
031A00
58/ 58
266/266
15
227A00
50.0/57.7 18.8/25.0
81.3/ 90.4
90/100
031A00
75/ 84
266/266
16
228A00
70.0/80.8 26.3/35.0
106.3/119.2
110/125
031A00
98/110
266/266
17
229A00
80.0/92.4 30.0/40.0
118.8/133.7
125/150
031A00
109/123
266/266
17
5.2
3.0
Low
Ċ
Ċ
Ċ/Ċ
52.1/ 52.1
60/ 60
Ċ
55/ 55
227/227
Ċ
225A00
20.0/23.1
7.5/10.0
52.1/ 52.1
60/ 60
031A00
55/ 55
227/227
15
226A00
30.0/34.6 11.3/15.0
53.8/ 59.0
60/ 60
031A00
55/ 55
227/227
15
227A00
50.0/57.7 18.8/25.0
78.8/ 87.9
80/ 90
031A00
72/ 81
227/227
16
228A00
70.0/80.8 26.3/35.0
103.8/116.7
110/125
031A00
96/108
227/227
17
229A00
80.0/92.4 30.0/40.0
116.3/131.2
125/150
031A00
107/121
227/227
17
10.2
High
Ċ
Ċ
Ċ/Ċ
57.1/ 57.1
70/ 70
Ċ
61/ 61
270/270
Ċ
225A00
20.0/23.1
7.5/10.0
57.1/ 57.1
70/ 70
030A00
61/ 61
270/270
15
226A00
30.0/34.6 11.3/15.0
60.0/ 65.2
70/ 70
030A00
61/ 61
270/270
15
227A00
50.0/57.7 18.8/25.0
85.1/ 94.1
90/100
031A00
78/ 87
270/270
16
228A00
70.0/80.8 26.3/35.0
110.1/123.0
125/125
031A00
101/114
270/270
17
229A00
80.0/92.4 30.0/40.0
122.6/137.4
125/150
031A00
113/127
270/270
17
460-3-60
414
506
7.1
46
0.8
2.6
Ċ
Low
Ċ
Ċ
Ċ
22.2
25
Ċ
24
112
Ċ
232A00
11.5
10.0
22.2
25
030A00
24
112
15
233A00
17.3
15.0
27.6
30
030A00
25
112
15
234A00
28.9
25.0
42.1
45
030A00
39
112
15
235A00
40.4
35.0
56.5
60
030A00
52
112
15
236A00
46.2
40.0
63.7
70
033A00
59
112
19
4.8
High
Ċ
Ċ
Ċ
24.4
30
Ċ
26
134
Ċ
232A00
11.5
10.0
24.4
30
030A00
26
134
15
233A00
17.3
15.0
30.4
35
030A00
28
134
15
234A00
28.9
25.0
44.8
45
030A00
41
134
15
235A00
40.4
35.0
59.2
60
030A00
54
134
15
236A00
46.2
40.0
66.5
70
033A00
61
134
19
LEGEND
FLA
− Full Load Amps
HACR − Heating, Air Conditioning and Refrigeration
IFM
− Indoor − Fan Motor
LRA
− Locked Rotor Amps
MCA
− Minimum Circuit Amps
MOCP − Maximum Overcurrent Protection
NEC
− National Electrical Code
OFM
− Outdoor−Fan Motor
RLA
− Rated Load Amps
*
Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribu-
tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
†
Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equip-
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than
2%.
Use the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
224 + 231 + 226
3
681
3
=
227
=
Determine maximum deviation from average voltage.
(AB) 227 – 223 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
= 100 x
4
227
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. Single point kits CRSINGLE028A00 and CRSINGLE030A00 are not required if
field−supplied pressure connectors are used.
50PG03−16