Carrier 50PG03-16 User Manual
Page 18

18
Table 1 — Electrical Data — Units Without Optional Powered Convenience Outlet (cont)
UNIT
50PG
NOMINAL
POWER
SUPPLY
VOLTS-PH-HZ
VOLTAGE
RANGE
COMPRESSOR
(EA.)
OFM
FLA
IFM
FLA
POWER
EXHAUST
FLA
IFM
TYPE
ELECTRIC
HEAT
POWER
SUPPLY
CRSINGLE
PART
NO.(NOTE3)
DISCONNECT
SIZE
WIRING
FIG.
NO.
MIN
MAX
RLA
LRA
CRHEATER
PART
NO.
FLA
NOMINAL
KW*
MCA
MOCP†
FLA
LRA
12
(cont)
575-3-60
518
632
6.1
40.0
0.8
2.8
Ċ
Low
Ċ
Ċ
Ċ
20.1
20
Ċ
21
124
Ċ
239A00
13.9
15.0
20.8
25
030A00
21
124
15
240A00
23.1
25.0
32.4
35
030A00
32
124
15
241A00
32.3
35.0
43.9
45
030A00
42
124
15
242A00
37.0
40.0
49.7
50
030A00
48
124
15
243A00
46.2
50.0
49.7
60
030A00
58
124
15
3.3
High
Ċ
Ċ
Ċ
18.6
20
Ċ
20
142
Ċ
239A00
13.9
15.0
21.4
25
030A00
20
142
15
240A00
23.1
25.0
33.0
35
030A00
30
142
15
241A00
32.3
35.0
45.1
45
030A00
41
142
15
242A00
37.0
40.0
50.3
50
030A00
46
142
15
243A00
46.2
50.0
50.3
60
030A00
57
142
15
2.8
3.0
Low
Ċ
Ċ
Ċ
21.1
25
Ċ
23
110
Ċ
239A00
13.9
15.0
24.6
25
030A00
23
110
15
240A00
23.1
25.0
36.1
40
030A00
33
110
15
241A00
32.3
35.0
47.7
50
030A00
44
110
15
242A00
37.0
40.0
53.4
60
030A00
49
110
15
243A00
46.2
50.0
53.4
60
030A00
60
110
15
3.3
High
Ċ
Ċ
Ċ
21.1
25
Ċ
23
110
Ċ
239A00
13.9
15.0
24.6
25
030A00
23
110
15
240A00
23.1
25.0
36.1
40
030A00
33
110
15
241A00
32.3
35.0
47.7
50
030A00
44
110
15
242A00
37.0
40.0
53.4
60
030A00
49
110
15
243A00
46.2
50.0
53.4
60
030A00
60
110
15
LEGEND
FLA
− Full Load Amps
HACR − Heating, Air Conditioning and Refrigeration
IFM
− Indoor − Fan Motor
LRA
− Locked Rotor Amps
MCA
− Minimum Circuit Amps
MOCP − Maximum Overcurrent Protection
NEC
− National Electrical Code
OFM
− Outdoor−Fan Motor
RLA
− Rated Load Amps
*
Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribu-
tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
†
Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equip-
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than
2%.
Use the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
224 + 231 + 226
3
681
3
=
227
=
Determine maximum deviation from average voltage.
(AB) 227 – 223 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
= 100 x
4
227
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. Single point kits CRSINGLE028A00 and CRSINGLE030A00 are not required if
field−supplied pressure connectors are used.
50PG03−16