Table 1 — Electrical Data — Units Without Optional Powered Convenience Outlet
UNIT
50PG
NOMINAL
POWER
SUPPLY
VOLTS−PH−HZ
VOLTAGE
RANGE
COMPRESSOR
(EA)
OFM
FLA
IFM
FLA
POWER
EXHAUST
FLA
IFM
TYPE
ELECTRIC
HEAT
POWER
SUPPLY
CRSINGLE
PART
NO.
(N
ote
3)
DISCONNECT
SIZE
WIRING
FIG.
NO.
MIN
MAX
RLA
LRA
CRHEATER
PART
NO.
FLA
NOMINAL
KW*
MCA
MOCP
{
FLA
LRA
03
208/230-1-60
187
253
12.8
60
0.9
4.9
Ċ
Low
Ċ
Ċ
Ċ/Ċ
21.8/21.8
30/30
Ċ
21/21
73/73
Ċ
200A00
10.8/12.5
2.3/ 3.0
21.8/21.8
30/30
028A00
21/21
73/73
13
201A00
17.3/20.0
3.8/ 5.0
27.8/31.1
30/35
028A00
26/29
73/73
13
202A00
26.0/30.0
5.6/ 7.5
38.6/43.6
40/45
028A00
36/40
73/73
13
203A00
34.7/40.0
7.5/10.0
49.5/56.1
50/60
028A00
45/52
73/73
13
High
Ċ
Ċ
Ċ/Ċ
21.8/21.8
30/30
Ċ
21/21
73/73
Ċ
200A00
10.8/12.5
2.3/ 3.0
21.8/21.8
30/30
028A00
21/21
73/73
13
201A00
17.3/20.0
3.8/ 5.0
27.8/31.1
30/35
028A00
26/29
73/73
13
202A00
26.0/30.0
5.6/ 7.5
38.6/43.6
40/45
028A00
36/40
73/73
13
203A00
34.7/40.0
7.5/10.0
49.5/56.1
50/60
028A00
45/52
73/73
13
1.4
Low
Ċ
Ċ
Ċ/Ċ
23.2/23.2
30/30
Ċ
23/23
75/75
Ċ
200A00
10.8/12.5
2.3/ 3.0
23.2/23.5
30/30
028A00
23/23
75/75
13
201A00
17.3/20.0
3.8/ 5.0
29.5/32.9
30/35
028A00
27/30
75/75
13
202A00
26.0/30.0
5.6/ 7.5
40.4/45.4
45/50
028A00
37/42
75/75
13
203A00
34.7/40.0
7.5/10.0
51.2/57.9
60/60
028A00
47/53
75/75
13
High
Ċ
Ċ
Ċ/Ċ
23.2/23.2
30/30
Ċ
23/23
75/75
Ċ
200A00
10.8/12.5
2.3/ 3.0
23.2/23.5
30/30
028A00
23/23
75/75
13
201A00
17.3/20.0
3.8/ 5.0
29.5/32.9
30/35
028A00
27/30
75/75
13
202A00
26.0/30.0
5.6/ 7.5
40.4/45.4
45/50
028A00
37/42
75/75
13
203A00
34.7/40.0
7.5/10.0
51.2/57.9
60/60
028A00
47/53
75/75
13
04
208/230-1-60
187
253
15.4
83
0.9
4.9
Ċ
Low
Ċ
Ċ
Ċ/Ċ
25.0/25.0
30/30
Ċ
24/24
96/96
Ċ
200A00
10.8/12.5
2.3/ 3.0
25.0/25.0
30/30
028A00
24/24
96/96
13
201A00
17.3/20.0
3.8/ 5.0
27.8/31.1
30/40
028A00
26/29
96/96
13
202A00
26.0/30.0
5.6/ 7.5
38.6/43.6
40/45
028A00
36/40
96/96
13
203A00
34.7/40.0
7.5/10.0
49.5/56.1
50/60
028A00
45/52
96/96
13
204A00
52.0/60.0 11.3/15.0
71.1/81.1
80/90
029A00
65/75
96/96
14
High
Ċ
Ċ
Ċ/Ċ
25.0/25.0
30/30
Ċ
24/24
96/96
Ċ
200A00
10.8/12.5
2.3/ 3.0
25.0/25.0
30/30
028A00
24/24
96/96
13
201A00
17.3/20.0
3.8/ 5.0
27.8/31.1
30/40
028A00
26/29
96/96
13
202A00
26.0/30.0
5.6/ 7.5
38.6/43.6
40/45
028A00
36/40
96/96
13
203A00
34.7/40.0
7.5/10.0
49.5/56.1
50/60
028A00
45/52
96/96
13
204A00
52.0/60.0 11.3/15.0
71.1/81.1
80/90
029A00
65/75
96/96
14
1.4
Low
Ċ
Ċ
Ċ/Ċ
26.4/26.4
40/40
Ċ
26/26
98/98
Ċ
200A00
10.8/12.5
2.3/ 3.0
26.4/26.4
40/40
028A00
26/26
98/98
13
201A00
17.3/20.0
3.8/ 5.0
29.5/32.9
40/40
028A00
27/30
98/98
13
202A00
26.0/30.0
5.6/ 7.5
40.4/45.4
45/50
028A00
37/42
98/98
13
203A00
34.7/40.0
7.5/10.0
51.2/57.9
60/60
028A00
47/53
98/98
13
204A00
52.0/60.0 11.3/15.0
72.9/82.9
80/90
029A00
67/76
98/98
14
High
Ċ
Ċ
Ċ/Ċ
26.4/26.4
40/40
Ċ
26/26
98/98
Ċ
200A00
10.8/12.5
2.3/ 3.0
26.4/26.4
40/40
028A00
26/26
98/98
13
201A00
17.3/20.0
3.8/ 5.0
29.5/32.9
40/40
028A00
27/30
98/98
13
202A00
26.0/30.0
5.6/ 7.5
40.4/45.4
45/50
028A00
37/42
98/98
13
203A00
34.7/40.0
7.5/10.0
51.2/57.9
60/60
028A00
47/53
98/98
13
204A00
52.0/60.0 11.3/15.0
72.9/82.9
80/90
029A00
67/76
98/98
14
208/230-3-60
187
253
11.5
77
0.9
4.9
Ċ
Low
Ċ
Ċ
Ċ/Ċ
20.2/20.2
30/30
Ċ
20/20
90/90
Ċ
207A00
6.3/ 7.2
2.3/ 3.0
20.2/20.2
30/30
030A00
20/20
90/90
15
208A00
10.0/11.5
3.8/ 5.0
20.2/20.6
30/30
030A00
20/20
90/90
15
209A00
15.0/17.3
5.6/ 7.5
24.9/27.8
30/30
030A00
23/26
90/90
15
210A00
20.0/23.1
7.5/10.0
31.1/35.0
35/40
030A00
29/32
90/90
15
211A00
30.0/34.6 11.3/15.0
43.6/49.4
45/50
030A00
40/45
90/90
15
High
Ċ
Ċ
Ċ/Ċ
20.2/20.2
30/30
Ċ
20/20
90/90
Ċ
207A00
6.3/ 7.2
2.3/ 3.0
20.2/20.2
30/30
030A00
20/20
90/90
15
208A00
10.0/11.5
3.8/ 5.0
20.2/20.6
30/30
030A00
20/20
90/90
15
209A00
15.0/17.3
5.6/ 7.5
24.9/27.8
30/30
030A00
23/26
90/90
15
210A00
20.0/23.1
7.5/10.0
31.1/35.0
35/40
030A00
29/32
90/90
15
211A00
30.0/34.6 11.3/15.0
43.6/49.4
45/50
030A00
40/45
90/90
15
LEGEND
FLA
− Full Load Amps
HACR − Heating, Air Conditioning and Refrigeration
IFM
− Indoor − Fan Motor
LRA
− Locked Rotor Amps
MCA
− Minimum Circuit Amps
MOCP − Maximum Overcurrent Protection
NEC
− National Electrical Code
OFM
− Outdoor−Fan Motor
RLA
− Rated Load Amps
*
Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribu-
tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
†
Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equip-
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than
2%.
Use the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
224 + 231 + 226
3
681
3
=
227
=
Determine maximum deviation from average voltage.
(AB) 227 – 223 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
= 100 x
4
227
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. Single point kits CRSINGLE028A00 and CRSINGLE030A00 are not required if
field−supplied pressure connectors are used.
50PG03−16