Table 2 — Electrical Data — Units With Optional Powered Convenience Outlet
UNIT
50PG
NOMINAL
POWER
SUPPLY
VOLTS-PH-HZ
VOLTAGE
RANGE
COMPRESSOR
(EA)
OFM
FLA
IFM
FLA
POWER
EXHAUST
FLA
IFM
TYPE
ELECTRIC
HEAT
POWER
SUPPLY
CRSINGLE
PART
NO.
(NOTE3)
DISCONNECT
SIZE
WIRING
FIG.
NO.
MIN
MA
X
RLA
LRA
CRHEATER
PART
NO.
FLA
NOMINAL
KW*
MCA
MOCP†
FLA
LRA
03
208/230-1-60
187
253
12.8
60
0.9
4.9
Ċ
Low
Ċ
Ċ
Ċ/Ċ
27.8/27.8
30/30
Ċ
27/27
78/78
Ċ
200A00
10.8/12.5
2.3/3.0
27.8/27.8
30/30
028A00
27/27
78/78
13
201A00
17.3/20.0
3.8/5.0
32.8/36.1
35/40
028A00
31/34
78/78
13
202A00
26.0/30.0
5.6/7.5
43.6/48.6
45/50
028A00
41/46
78/78
13
203A00
34.7/40.0
7.5/10.0
54.5/61.1
60/70
028A00
51/57
78/78
13
High
Ċ
Ċ
Ċ/Ċ
27.8/27.8
30/30
Ċ
27/27
78/78
Ċ
200A00
10.8/12.5
2.3/3.0
27.8/27.8
30/30
028A00
27/27
78/78
13
201A00
17.3/20.0
3.8/5.0
32.8/36.1
35/40
028A00
31/34
78/78
13
202A00
26.0/30.0
5.6/7.5
43.6/48.6
45/50
028A00
41/46
78/78
13
203A00
34.7/40.0
7.5/10.0
54.5/61.1
60/70
028A00
51/57
78/78
13
1.4
Low
Ċ
Ċ
Ċ/Ċ
29.2/29.2
40/40
Ċ
29/29
80/80
Ċ
200A00
10.8/12.5
2.3/3.0
29.2/29.2
40/40
028A00
29/29
80/80
13
201A00
17.3/20.0
3.8/ 5.0
34.5/37.9
40/40
028A00
33/36
80/80
13
202A00
26.0/30.0
5.6/ 7.5
45.4/50.4
50/60
028A00
43/47
80/80
13
203A00
34.7/40.0
7.5/10.0
56.2/62.9
60/70
028A00
53/59
80/80
13
High
Ċ
Ċ
Ċ/Ċ
29.2/29.2
40/40
Ċ
29/29
80/80
Ċ
200A00
10.8/12.5
2.3/ 3.0
29.2/29.2
40/40
028A00
29/29
80/80
13
201A00
17.3/20.0
3.8/ 5.0
34.5/37.9
40/40
028A00
33/36
80/80
13
202A00
26.0/30.0
5.6/ 7.5
45.4/50.4
50/60
028A00
43/47
80/80
13
203A00
34.7/40.0
7.5/10.0
56.2/62.9
60/70
028A00
53/59
80/80
13
04
208/230-1-60
187
253
15.4
83
0.9
4.9
Ċ
Low
Ċ
Ċ
Ċ/Ċ
31.0/31.0
45/45
Ċ
30/30
101/101
Ċ
200A00
10.8/12.5
2.3/ 3.0
31.0/31.0
45/45
028A00
30/30
101/101
13
201A00
17.3/20.0
3.8/ 5.0
32.8/36.1
45/45
028A00
31/34
101/101
13
202A00
26.0/30.0
5.6/ 7.5
43.6/48.6
45/50
028A00
41/46
101/101
13
203A00
34.7/40.0
7.5/10.0
54.5/61.1
60/70
028A00
51/57
101/101
13
204A00
52.0/60.0
11.3/15.0
76.1/86.1
80/90
029A00
71/80
101/101
14
High
Ċ
Ċ
Ċ/Ċ
31.0/31.0
45/45
Ċ
30/30
101/101
Ċ
200A00
10.8/12.5
2.3/ 3.0
31.0/31.0
45/45
028A00
30/30
101/101
13
201A00
17.3/20.0
3.8/ 5.0
32.8/36.1
45/45
028A00
31/34
101/101
13
202A00
26.0/30.0
5.6/ 7.5
43.6/48.6
45/50
028A00
41/46
101/101
13
203A00
34.7/40.0
7.5/10.0
54.5/61.1
60/70
028A00
51/57
101/101
13
204A00
52.0/60.0
11.3/15.0
76.1/86.1
80/90
029A00
71/80
101/101
14
1.4
Low
Ċ
Ċ
Ċ/Ċ
32.4/32.4
45/45
Ċ
32/32
103/103
Ċ
200A00
10.8/12.5
2.3/ 3.0
32.4/32.4
45/45
028A00
32/32
103/103
13
201A00
17.3/20.0
3.8/ 5.0
34.5/37.9
45/45
028A00
33/36
103/103
13
202A00
26.0/30.0
5.6/ 7.5
45.4/50.4
50/60
028A00
43/47
103/103
13
203A00
34.7/40.0
7.5/10.0
56.2/62.9
60/70
028A00
53/59
103/103
13
204A00
52.0/60.0
11.3/15.0
77.9/87.9
80/90
029A00
73/82
103/103
14
High
Ċ
Ċ
Ċ/Ċ
32.4/32.4
45/45
Ċ
32/32
103/103
Ċ
200A00
10.8/12.5
2.3/ 3.0
32.4/32.4
45/45
028A00
32/32
103/103
13
201A00
17.3/20.0
3.8/ 5.0
34.5/37.9
45/45
028A00
33/36
103/103
13
202A00
26.0/30.0
5.6/ 7.5
45.4/50.4
50/60
028A00
43/47
103/103
13
203A00
34.7/40.0
7.5/10.0
56.2/62.9
60/70
028A00
53/59
103/103
13
204A00
52.0/60.0
11.3/15.0
77.9/87.9
80/90
029A00
73/82
103/103
14
208/230-3-60
187
253
11.5
77
0.9
4.9
Ċ
Low
Ċ
Ċ
Ċ/Ċ
25.0/25.0
30/30
Ċ
25/25
95/95
Ċ
207A00
6.3/ 7.2
2.3/ 3.0
25.0/25.0
30/30
030A00
25/25
95/95
15
208A00
10.0/11.5
3.8/ 5.0
25.0/26.0
30/30
030A00
25/25
95/95
15
209A00
15.0/17.3
5.6/ 7.5
30.9/33.2
35/35
030A00
28/31
95/95
15
210A00
20.0/23.1
7.5/10.0
37.2/40.4
40/45
030A00
34/38
95/95
15
211A00
30.0/34.6
11.3/15.0
49.7/54.9
50/60
030A00
46/51
95/95
15
High
Ċ
Ċ
Ċ/Ċ
25.0/25.0
30/30
Ċ
25/25
95/95
Ċ
207A00
6.3/ 7.2
2.3/ 3.0
25.0/25.0
30/30
030A00
25/25
95/95
15
208A00
10.0/11.5
3.8/ 5.0
25.0/26.0
30/30
030A00
25/25
95/95
15
209A00
15.0/17.3
5.6/ 7.5
30.9/33.2
35/35
030A00
28/31
95/95
15
210A00
20.0/23.1
7.5/10.0
37.2/40.4
40/45
030A00
34/38
95/95
15
211A00
30.0/34.6
11.3/15.0
49.7/54.9
50/60
030A00
46/51
95/95
15
LEGEND
FLA
− Full Load Amps
HACR − Heating, Air Conditioning and Refrigeration
IFM
− Indoor − Fan Motor
LRA
− Locked Rotor Amps
MCA
− Minimum Circuit Amps
MOCP − Maximum Overcurrent Protection
NEC
− National Electrical Code
OFM
− Outdoor−Fan Motor
RLA
− Rated Load Amps
*
Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribu-
tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
†
Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equip-
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than
2%.
Use the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
224 + 231 + 226
3
681
3
=
227
=
Determine maximum deviation from average voltage.
(AB) 227 – 223 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
= 100 x
4
227
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. Single point kits CRSINGLE028A00 and CRSINGLE030A00 are not required if
field−supplied pressure connectors are used.