beautypg.com

Cable tray sizing flowchart – Cooper Bussmann CT02MAN User Manual

Page 55

background image

53

Cable Tray Manual

Cooper B-Line, Inc

CABLE TRAY SIZING FLOWCHART

Appendix Sheet 8

392.9(E)(1)

W x D ≥ 1.6A

392.9(A)(1)

W ≥ Sd

(single layer)

392.9(C)(1)

W ≥ Sd/0.9
(single layer)

Note: The value “A”

only applies to cables

smaller than 4/0.

The value “Sd” only

applies to 4/0 and

larger cables, which
must be single layer

Note: The value “A”

only applies to cables

smaller than 4/0.

The value “Sd” only

applies to 4/0 and

larger cables, which
must be single layer

392.9(A)(3)

Vented

Channel

Tray

Solid

Channel

Tray

Solid

Bottom

Tray

Ladder

or Vented

Trough

Tray

One M/C

only

M/C 4/0

or larger

M/C 4/0

or larger

392.9(E)(2)

W x D ≥ 2.9A

392.9(F)(1)

W x D ≥ 1.9A

392.9(F)(2)

W x D ≥ 3.2A

392.9(A)(2)

W ≥ A/1.2

392.9(C)(2)

W ≥ A/0.9

M/C

smaller

than 4/0

One

M/C
Only

M/C

smaller

than 4/0

M/C

smaller than

4/0, with

4/0 or

larger

M/C

control

and/or

signal

W ≥ A/1.2 + Sd

No

No

No

No

No

No

No

No

No

No

392.9(B)

W x D ≥ 2A

392.9(C)(3)

A + Sd

0.9

M/C

smaller than

4/0, with

4/0 or

larger

M/C

control

and/or

signal

W ≥

392.9(D)

W x D ≥ 2.5A

Yes

Yes

Yes

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Legend

W = Cable Tray Width

D = Cable Tray Load Depth

Sd = Sum of Cable Diameters

A = Sum of Cable Areas
S/C = Single Conductor

M/C = Multiconductor Cables

RS = Ladder Rung Spacing

Ampacity: See pages 36 - 38 for information on cable ampacity that

might affect the cable tray sizing flowchart.

See pages 15 - 17 for information on hazardous
(classified) areas that might affect the cable tray sizing
flowchart.