Cable Tray Manual
Cooper B-Line, Inc
Appendix Sheet 7
Reprinted with permission from NFPA 70-1999, the National Electrical Code®, Copyright© 1998, National Fire
Protection Association, Quincy, MA 02269. This reprinted material is not the complete and official position of the National
Fire Protection Association, on the referenced subject which is represented only by the standard in its entirety.
Table 250.122. Minimum Size Equipment Grounding
Conductors for Grounding Raceways and Equipment
Rating or Setting of
Size
Automatic Overcurrent
(AWG or kcmil)
Device in Circuit Ahead
of Equipment, Conduit,
Aluminum or
etc., Not Exceeding
Copper-Clad
(Amperes)
Copper
Aluminum*
15
14
12
20
12
10
30
10
8
40
10
8
60
10
8
100
8
6
200
6
4
300
4
2
400
3
1
500
2
1/0
600
1
2/0
800
1/0
3/0
1000
2/0
4/0
1200
3/0
250
1600
4/0
350
2000
250
400
2500
350
600
3000
400
600
4000
500
800
5000
700
1200
6000
800
1200