30ra/30rh, Troubleshooting, Gb - 14 – Carrier AQUASNAP 30RH User Manual
Page 15
30RA/30RH
GB - 14
Troubleshooting
A list of possible faults, as well as the probable cause and
suggested solutions is shown as follows. In the event of a unit
malfunction it is recommended to disconnect the power supply and
ascertain the cause.
Symptoms
Cause
REMEDY
Unit does not start:
- No power supply;
CONNECT
POWER
SUPPLY
.
- Main switch open;
CLOSE
SWITCH
.
- Low line voltage;
CHECK
VOLTAGE
AND
REMEDY
THE
DEFICIENCY
.
- A protection has tripped;
RESET
.
- Contactor stuck open;
CHECK
AND
IF
NECESSARY
REPLACE
CONTACTOR
.
- Seized compressor;
CHECK
AND
IF
NECESSARY
REPLACE
COMPRESSOR
.
- Loose electrical connections;
CHECK
CONNECTIONS
.
Unit runs continuously or starts and stops frequently:
- Defective compressor contactor;
-
CHECK
AND
IF
NECESSARY
REPLACE
CONTACTOR
.
- Defective compressor;
CHECK
AND
IF
NECESSARY
REPLACE
COMPRESSOR
.
- Refrigerant losses;
CHECK
AND
ADD
THE
NECESSARY
QUANTITY
.
- Total water flow too low
CHECK
FOR
PRESSURE
DROP
IN
THE
HYDRAULIC
CIRCUIT
.
-
Static pressure in the hydraulic circuit too low;
CHECK
IT
ON
THE
PRESSURE
GAUGE
AND
RESTORE
IT
IF
NECESSARY
.
Unit continuously cuts out at low pressure:
- Refrigerant losses;
CHECK
AND
ADD
THE
NECESSARY
QUANTITY
.
- Low water flow in the exchanger;
CHECK
WATER
PUMP
.
- Unit start-up delay;
WAIT
UNTIL
THE
SYSTEM
HAS
STABILISED
.
Unit continuously cuts out at high pressure:
- Defective high pressurestat;
CHECK
AND
IF
NECESSARY
REPLACE
PRESSURESTAT
.
- Blocked expansion valve;
CHECK
AND
REPLACE
IF
NECESSARY
.
- Blocked filter drier;
CHECK
AND
IF
NECESSARY
REPLACE
FILTER
.
- The outdoor fan/s does/do not work;
CHECK
THE
CONDITION
OF
THE
FAN
MOTOR
/
S
AND
ITS
/
THEIR
ELECTRICAL
CONNECTIONS
.
-
Obstructed or dirty battery;
REMOVE
THE
OBSTRUCTION
OR
CLEAN
THE
BATTERY
.
Abnormal system noise:
- Piping vibration;
SUPPORT
PIPING
.
- Noisy compressor;
CHECK
AND
CHANGE
IF
NECESSARY
.
- Hissing expansion valve;
CHECK
AND
ADD
REFRIGERANT
IF
NECESSARY
.
- Badly fitting panels;
INSTALL
CORRECTLY
.
Compressor loses oil:
- Leaking refrigeration circuit;
REPAIR
LEAK
.
Water loss:
- Defective entering or leaving connections;
CHECK
AND
TIGHTEN
IF
NECESSARY
.
The unit does not defrost
(only for 30RH units):
- Four-way reversing valve faulty;
CHECK
AND
REPLACE
THE
VALVE
IF
NECESSARY
.
- Defrost sensor broken;
CHECK
AND
REPLACE
THE
SENSOR
IF
NECESSARY
.