beautypg.com

Models, Features – Dynalco SST-2400H Speed Switch/Transmitter User Manual

Page 7

background image

Models

Model

No. Of

Set Points 3rd Party Certification(s)

A series – standard relays

SST-2000A

0

CSA: general certification LR 92270
ABS: type approval
CE: 89/336/EEC, Light Industrial
CE: 72/23/EEC, Low Voltage Directive

SST-2200A

2

SST-2400A

4

H series – hermetically sealed relays

SST-2000H

0

CSA: Class I, Div. 2, Grp. D, LR 45322*
CE: 89/336/EEC, Light Industrial
CE: 72/23/EEC, Low Voltage Directive

SST-2200H

2

SST-2400H

4

* Approval contingent upon housing an SST-2000H series device in a CSA-certified

enclosure.

Features

Signal

Sources

Field-programmable for: sensors, including contact closure input,

magnetic pickups, ac generators, contact closures, photocells.

Input

Frequency

t

Full-scale values from 0–0.1 Hz (6 pulses/minute) to 0-20 kHz.

t

Field-adjustable range and sensitivity control.

Alarm Set

Points

0 SST-2000A/H (when only proportional output is required)
2 SST-2200A/H
4 SST-2400A/H

Alarm

Settings

Alarms are field-configurable for overspeed, underspeed,

energize, de-energize, latch, auto-reset.

Alarm

Disable

Disable all alarms (for startup conditions and special functions)

Alarm Reset

t

Momentarily reset all latched alarms

t

Permanently converts all latching alarms to auto-reset

Set Point

Verification

Integral VERIFY permits viewing and setting of set point value

without actuating the relays. Requires an external meter.

Proportional

Outputs

0–1 mA and 4–20 mA (standard)
0–5 Vdc or 0–10 Vdc (field-selectable)

Output

Power

Repeater output drives counters and self-powered tachometers.

Regulated 14 Vdc output powers active pickups, accessories, and

meters (e.g. DPM-105; MTH-103D; SPD-100L; LST-100L).

Output

Range

Current source up to 50 mAdc output always included.

4

Chapter 1