Programming Set Points and Relays

Remove the top plate from the SST-2000A/H to reveal DIP switches B and C.

Use DIP switches B and C to program relay set points to:

t

energize (OFF) / de-energize (ON) on alarm

t

non-latch (OFF) / latch (ON) on alarm

t

actuate SPST (OFF) / DPDT (ON) trip on alarm

t

change proportional voltage output

The underside of the top plate contains labels for each DIP switch setting.

Resetting a latched relay

To momentarily reset a latched relay, jumper terminals 32 and 7.

25

Calibrating the Speed Switch

Fig. 4-11

The DIP switch settings

available to you depend on the model
of speed switch you purchased:

t

SST-2400A/H series switches have

four set point relay adjustments

(DIP switches B and C).

t

SST-2200A/H series switches only

have relays 1 and 2 (adjustable

using DIP switch C).

t

SST-2000A/H switches have no set

point relays.