t

Confirm the meter is properly connected to the SST-2000A/H.

t

Use a frequency generator (e.g. F-16) to apply full-scale frequency
to terminal 5 (HI) & 6 (COM) on the SST-2000A/H. Maximum
signal input is 50 Vrms for a standard unit.

t

Adjust the

METER CALIBRATE

potentiometer on the

SST-2000A/H for the appropriate full-scale reading on each
DPM-105.

t

Use a DPM-105 data sheet, if necessary, to calibrate the
DPM-105 meters.

Connecting more than one DPM-105

1

Remove the jumper across terminals 1 and 2 on each DPM-105.

2

Connect the meters as shown in Fig. 3-4.

3

Calibrate the SST-2000A/H.

t

Confirm the meter is properly connected to the SST-2000A/H.

t

Apply full-scale frequency to terminal5 (HI) & 6 (COM) on the
SST-2000A/H. Maximum signal input is 50 Vrms for a standard
unit.

t

Adjust the

ME TER CAL I BRATE

po ten ti om e ter on the

SST-2000A/H for the ap pro pri ate full -scale read ing on each
DPM-105.

t

Use a DPM-105 data sheet, if necessary, to calibrate the
DPM-105 meters.

15

Powering External Devices

Fig. 3-4

Connecting

more than one DPM-105
to the SST-2000A/H.