Set points 3 & 4 and selecting DPDT trip

THE EFFECT OF TURNING B SWITCHES ON

Turn on B to...

B1 LATCH set point 3 on alarm

B2 ACTUATE relay 4 simultaneously with relay 2, creating two Form

C contacts for set point 2 (DPDT relay).

B3 LATCH set point 4 on alarm

B4 ACTUATE relay 3 simultaneously with relay 1, creating two Form

C contacts for set point 1 (DPDT relay).

B5 DE-ENERGIZE relay 3 on alarm

B6 DE-ENERGIZE relay 4 on alarm

B7 ACTUATE set point 4 on overspeed.

B8 ACTUATE set point 3 on overspeed.

Set points 1 & 2: 0–5 & 0–10 Vdc proportional output

THE EFFECT OF TURNING C SWITCHES ON

Turn on C to...

C1 Change proportional output to 0-5 Vdc*. Confirm C2 is OFF.

C2 Changes proportional output to 0-10 Vdc*. Confirm C1 is OFF.

C3 DE-ENERGIZE relay 2 on alarm.

C4 ACTUATE relay 1 on overspeed, non-latch.

C5 LATCH relay 1 on alarm.

C6 LATCH relay 2 on alarm.

C7 ACTUATE relay 2 on overspeed, non-latch.

C8 DE-ENERGIZE relay 1 on alarm.

* Requires recalibration.

26

Chapter 4

EXAMPLE: To change
the proportional
output to 0–10 Vdc,
and set relay 2 to
actuate, energize,
and latch on
overspeed, turn on
C2, C6, and C7.

EXAMPLE: To set
relays 3 and 4 to
actuate, de-energize,
and latch on
overspeed, turn on
B1, B3, B5, B6, B7,
and B8.

t

the proportional

output is 4-20 mA

t

relays 1 and 2 are

energized,

underspeed

t

non-latched

WHEN ALL C

SWITCHES ARE OFF

t

relays 3 and 4 are

energized,

underspeed

t

non-latching

t

all relays are SPST