beautypg.com

Dynalco UM-200 Tachometer / Hourmeter / Monitor User Manual

Page 8

background image

7

Configuration of “Run Signal”


Using the arrows on the keypad, select the “Run Signal” icon.

There are (3) run types available. The definitions are as follows:

None: No run indication required. Monitoring is always active.
RPM: Monitoring is active when signal received from magnetic pickup.
Digital: Monitoring is active when contact closure (connection to ground) is sensed.

To select run signal type, use the up / down arrows to select, then press enter.

If “None” is selected, there is no other action required other than to select “escape.” After
selecting escape, you will be asked to select “yes” to save.

If “RPM” is selected, you will need to set the # gear teeth, RPM threshold and startup delay.
The RPM threshold is the speed above which monitoring will be active. The startup delay
allows you to delay monitoring for as many as 300 seconds (5 minutes) to allow time for all
inputs to be at normal levels. If no delay is required, set to 0 seconds. The magnetic pickup
input terminals are indicated on page 3.

If “Digital” is selected, you will only need to set the startup delay (if applicable). In this mode,
a run signal will be sensed with a contact closure (or short) between the magnetic pickup
input terminals indicated on page 3.


Pressing

at any time during configuration will prompt you to save the changes.

Select “Yes” to save any changes made. Selecting “No” will not save changes.


Configuration of each “Channel”

Using the arrows on the keypad, select the “Channel” icon.


Next, select the channel number to configure by pressing the up / down arrows and pressing
enter. Use the right

arrow to navigate and select the following:


Enable Channel

Yes / No

Channel Type

(0-1 V, 0-5 V, 0-10 V, 4-20 mA, J Type, K Type)

Description

(name

input with up to 20 characters)

Engineering Units

(up to 3 characters for PSI, F, C etc…)

Note: For thermocouple inputs, you must enter either “F” or “C”

Enable alarms

(read only or alarm?)

Alarm Type

(latching or non-latching)

Alarm

Output

(select to enable output trip)

Alarm

Low

(select

threshold for under-trip)

Alarm

High

(select

threshold for over-trip)

Alarm Reset Points

(select either the default reset value or manually set)

Alarm Reset Low

(manually set reset hysteresis for low trip)

Alarm Reset High

(manually set reset hysteresis for high trip)