Kenco Engineering KUSG Switch User Manual
Page 4
Specifications
Description
Specification
AC
115Vac or 230Vac; 50/60Hz
Input Power
DC
12 or 24Vdc
Output
10A DPDT
Switch
-20°F to 170°F
Temperature Range
Sensor (Metal)
-40°F to 300°F
Metal Sensors
Vacuum to 1000psig
Pressure Range
Non-metal Sensors
Vacuum to 100psig
Sensitivity (Signal-to-noise Ratio)
1000:1
Repeatability
±2mm
Response Time
0.5 sec. non-adjustable
TROUBLESHOOTING
Problem
Solution
Check wiring; verify that the correct input
voltage is applied
Verify that liquid is filling the sensor gap
Check for dense foam or dried product in
the gap. Switch may not function properly
if either condition exists.
Check sensor phono plugs for a good
connection. Unplug and Re-plug each
connection.
No output change with level change
Check for excessive aeration in process
fluid. This is particularly important in
viscous fluids.
Check wiring; verify that the correct input
voltage is applied
Check for turbulence. Relocate switch or
isolate from turbulence
The output is “chattering”
Check for excessive aeration in process
fluid. This is particularly important in
viscous fluids.